beautypg.com

10 extra codes and accessories – JUMO 706030 LOGOPRINT 500 Printing Recorder Operating Manual User Manual

Page 92

background image

10 Extra codes and accessories

92

10.2 “8 logic inputs”, “interface for ER8”,

“voltage output”

The Extra Code provides 8 logic inputs, the serial interface for the external re-
lay module ER8, and an electrically isolated power supply for 2-wire transmit-
ters.

The eight logic inputs can operated by floating contacts or by the following
voltage levels:
inactive

0 — 5V

active

20 — 35V

The voltage levels must be applied for at least 0.4sec.

Possible functions:

- external text

- binary-linked external text

- external start/stop

- change chart drive over to external speed

- event counter

- start scaling print

- start/stop of external report

- inhibit keys

- event traces