3 operation and visualisation – JUMO 706030 LOGOPRINT 500 Printing Recorder Operating Manual User Manual
Page 39

39
3 Operation and visualisation
External report
The external report is controlled by a selectable logic input. In addition to the
parameter Configuration level 2
Î
Report (EXTERN.CONTACT), the logic input
which is wanted must be selected through the parameter Configuration level 3
Î
External report (e.g. LOG.INPUT 6). The statistical period starts when the
logic input is closed. The report is printed out when the logic input is opened
(negative-edge triggering).
As a result of the expansion to two reports from software version 105.02.XX,
up to two external reports are now available.
Colour
assignment
The colour which is used to print the instrument designation can be defined
with the aid of the setup program (basic setting: black).
The minimum, maximum and average values are printed in the same colours
as the corresponding measurement traces. The colours for the traces can also
be altered in the setup program.
H
When the external report is used, the setting for the parameter
Configuration level 2
Î
Report must define whether it uses the first
or second istance of the report.
Right:
Configuration level 2
Î
1. Report = EXTERNAL CONTACT
Configuration level 3
Î
1. External report = Logic inp. 8
Wrong:
Configuration level 2
Î
2. Report = EXTERNAL CONTACT
Configuration level 3
Î
1. External report = Logic inp. 8