beautypg.com

2 open-collector outputs, Open-collector outputs, 3 operation and visualisation – JUMO 706030 LOGOPRINT 500 Printing Recorder Operating Manual User Manual

Page 25

background image

25

3 Operation and visualisation

3.2 Open-collector outputs

The printing recorder is equipped with four open-collector outputs. The out-
puts 1 to 3 have a fixed assignment to the limit comparators 1 to 3. Output 4 is
used as a fault signal output. The outputs can be activated by using the pa-
rameter Configuration level 2

Î

Open-collector.

Fault output

The fault signal output can be used to indicate a fault. During correct operation
of the printing recorder this output is active. In the event of a fault or distur-
bance, or if the status in the parameter Configuration level 2

Î

Open-collector

is OFF, it becomes inactive (open).

The following causes will lead to a fault signal:

- Chart paper end

- Power off

- The battery of the recorder is discharged

- No communication with the external relay module ER8

- Fatal errors