8 Fault messages and alarms
Data cable
faulty
Communication between master and slave
interrupted.
Check the patch cable and replace, if
necessary
Synchronization
failed
Slave device switched off or communica-
tion between master and slave interrupted
Check plug connection of patch cable
or voltage supply
M/S incompatible
#0002...0008
- Master and slave are incompatible
- Different power controller types
used (max. load current, load volt-
age and subordinate control loop (if
applicable) do not match)
Use same power controller types with
same software versions.
#0002
Different device software versions
Update devices to same device soft-
ware versions
v Service hotline
#0003
VDN numbers of devices do not match
Master/slave operation not possible
#0006
Different nominal voltages (device types) of
master and slave device.
Master/slave operation not possible
#0007
Different nominal currents (device types) of
master and slave device.
#0008
Set subordinate control loop of the master
is not compatible with that of the slave de-
vice.
Change subordinate control loops of
both devices to U or U
2
.
Teach-in
load monitoring!
Reminder that "manual" teach-in has been
configured but not yet executed.
Perform teach-in
v Chapter 6.1 "Detection of load
Slave: Limit value
Min. value reached
The value has gone below the set limit val-
ue for the min. alarm at the slave
Check why the value has gone below
the limit value.
Slave: Limit value
Max. value reached
The set limit value for the max. alarm has
been exceeded at the slave
Check why the limit value has been ex-
ceeded.
Slave: Fault at
connected load
Break or short-circuit of a load resistor.
v Chapter 6.1 "Detection of load
Replace defective heating elements.
Slave:
Blown fuse
(red LED fuse is lit)
1. Semi-conductor fuse defective
v Chapter 8.2 "Replacing a defec-
2. No voltage at terminal U1
- Check wiring
- Check the line fuse for the load
circuit
Slave:
SCR breakage
SCR defective
The device must be returned to JUMO
for repair.
h Return the device
Slave: SCR
short circuit
SCR defective
The device must be returned to JUMO
for repair.
h Return the device