beautypg.com

3 analog inputs, Analog inputs, Chapter 5.1.3 "analog inputs – JUMO 709061 TYA 201 - Single-Phase Power Controller Operating Manual User Manual

Page 60: 5 configuration

background image

5 Configuration

58

2012-12-01/00561071 [SCR Power Controller TYA201]

5.1.3

Analog inputs

The power controller has a voltage and a current input.
These inputs (default setpoint value) specify the output to be provided by the
power controller at the load output.

In most cases, this signal is sent as a standard signal from an electronic con-
troller or PLC and is adjusted with these settings.

1.

Analog input inverting:

If, for example, the current measuring range start is set to 20 mA and the current measuring range en
to 0 mA, the power controller is switched off at 20 mA and switched on at 0 mA.

Value/settings

Description

Current measuring
range

0 to 20 mA

This setting specifies which current standard signal is con-
nected.

v Chapter 3.3 "Connection diagram"

4 to 20 mA
Customer-specific

1

Current measuring
range, start

0 to 20 mA

Note: This parameter only appears if "Customer specific" is
set for the current measuring range (see above)!

Current measuring
range, end

0 to 20 mA

Note: This parameter only appears if "Customer specific" is
set for the current measuring range (see above)!

Voltage measuring
range

0 to 10 V

This setting specifies which voltage standard signal is con-
nected.

v Chapter 3.3 "Connection diagram"

2 to 10 V
0 to 5 V
1 to 5 V
Customer-specific

1

Voltage measuring
range, start

0 to 10 V

Note: This parameter only appears if "Customer specific" is
set for the voltage measuring range (see above)!

Voltage measuring
range, end

0 to 10 V

Note: This parameter only appears if "Customer specific" is
set for the voltage measuring range (see above)!

k

/ bold = factory setting