8 fault messages and alarms – JUMO 709061 TYA 201 - Single-Phase Power Controller Operating Manual User Manual
Page 96
8 Fault messages and alarms
94
2012-12-01/00561071 [SCR Power Controller TYA201]
Attention!
High temperature
Device temperature is higher than 100 °C
(excess temperature)
- Ensure adequate ventilation or
provide for additional cooling
- Reduce load current
- Use power controller with high-
er maximum load current
Limiting active
high temperature
Device temperature is higher than 105 °C .
Device is too hot, output level is reduced!
(limited power due to excess temperature)
- Ensure adequate ventilation or
provide for additional cooling
- Reduce load current
- Use power controller with high-
er maximum load current
Supply voltage is
too low
Supply voltage is not within specified toler-
ance range
v Chapter 10.1 "Voltage supply, load
Check nominal voltage of the device
type
Supply voltage is
too high
Supply voltage is not within specified toler-
ance range
Chapter 10.1 "Voltage supply, load cur-
rent"
Check nominal voltage of the device
type
Temporary
drop in supply
Dangerous temporary equal proportion for
transformer loads has been detected.
Ensure stable mains supply.
Master-slave
rotary field error
Counterclockwise rotary field has been de-
tected
Master-slave
incorrectly wired.
Wiring fault has been detected
Rotary field detec-
tion
failed
Rotary field detection not possible
- Check connection
v Chapter 3.3 "Connection dia-
- Eliminate line disturbances
Wire break
Current input
Input current too small for the set measur-
ing range.
- Check wiring for wire breaks and
reverse polarity.
- Check upstream devices (con-
trollers)
Wire break
Voltage input
Input voltage too small for the set measur-
ing range.
- Check wiring for wire breaks and
reverse polarity.
- Check upstream devices (con-
trollers)
Malfunction
Bus error
No connection to the Profibus master
Check wiring and master device (PLC).
Master-slave
Error in comm.
Error in the data transfer between master
and slave
Is the patch cable plug connected cor-
rectly?
Fault message
Cause
Remedy