beautypg.com

3 default setpoint value via potentiometer, 4 dual energy management, Default setpoint value via potentiometer – JUMO 709061 TYA 201 - Single-Phase Power Controller Operating Manual User Manual

Page 76: Dual energy management, Chapter 6.4 "dual energy management, 6 special device functions

background image

6 Special device functions

74

2012-12-01/00561071 [SCR Power Controller TYA201]

6.3 Default setpoint value via potentiometer

For this, a 5 k

Ω

potentiometer is connected to the voltage input.

It is supplied with DC 10 V at terminal 5 of the power controller.

h Configuration level

r

Analog inputs

r

Set voltage measuring range 0 to

10 V

h Configuration level

r

Setpoint value config.

r

Default setpoint value

r

Set

voltage input

Now the power controller power is preset via the external potentiometer.

6.4 Dual energy management

This allows setpoint values of up to 50 % each to be preset on 2 power con-
trollers without causing current peaks in the network when they are switched
on simultaneously.
No current peaks are caused in the network even if the setpoint values are
asymmetrically distributed, e.g. 30 % and 70 %.

More than
2 power con-
trollers

If more than 2 power controllers are required in a system, they must be divided
into 2 groups.
The "Dual energy management" parameter (Device1 and Device2) has to be
set in each group.

Pre-
requisites

- Both devices must be connected to the same phase
- The control electronics and the load circuit must have the same phase
- Synchronize both devices by switching them on simultaneously
- Burst-firing mode must be configured
- The cycle time must be set to 500 ms (fixed)
- In each group, one TYA201 power controller must be configured as

Device1 and the other TYA201 power controller as Device2.

A

S

E