3 Electrical connection

28

2012-12-01/00561071 [SCR Power Controller TYA201]

3.2.3 Type 709061/X-0X-100-XXX-XXX-XX-25X

Devices with a load current of 100 A are equipped with plug-in screw terminals
in the control section and cable lugs in the power section.

Terminal

Version

Conductor cross-section

Maximum
tightening
torque

X2_1 and X2_2

Slotted screws, blade width 2 mm

0.2 to 1.5 mm

2

0.25 Nm

X3

Slotted screws, blade width 3 mm

0.5 to 2.5 mm

2

0.5 Nm

U2, U1

M6 hexagon screws, width across
flats 10 mm

16 to 50 mm

2

5 Nm

For applications according to UL, only 75 °C copper conductors may be used!

N/L2, V, L1

Slotted screws,
blade width 3 mm

0.5 to 4 mm

2

or

(0.5 to 2.5 mm

2

with ferrule)

(for UL application AWG 20-
12)

0.5 Nm

Ground terminal
PE

M6 setscrew with hexagon nut
Width across flats 10 mm

Cable lug
hole: 6 mm

5 Nm