5 Configuration
Cycle time
Fixed (500 ms)
(For slow heating ele-
ments)
Note:
This setting is only available in burst-firing mode.
For example, for a fixed period of 500 ms, 5 sine waves are
switched on and 20 switched off at an output level of 20 %.
Fastest possible
(For quick-response
heating elements)
With this setting, the cycle time is variable. At the required out-
put level, the device attempts to find the shortest possible cy-
cle time for entire sine wave cycles. At an output level of 20 %,
this relates to one sine wave ON and four sine waves OFF.
Min. ON period
None
3 full sine waves
Dependent on the cycle time setting.
At least 3 full sine waves are always let through.
At an output level of 50 % and fastest possible cycle time,
3 sine waves are switched on and 3 switched off.
Note:
Particularly suitable for the control of transformer loads
α
start
No
Note:
This setting is available in continuous burst-firing mode and in
logic operation.
No: for resistive load
Yes: for transformer loads
If set to "Yes", the first half-wave of each pulse group is cut
with the set phase control angle
α
.
Yes
Angle
α
start
0 to 70 to 90 °el
Phase control angle for
α
start
Soft start
No
This setting determines the starting behavior of the power
controller after power ON and is deactivated ex works.
Value/settings
Description
k
/ bold = factory setting
u
t
500ms
5
20
u
t
500ms
5
20
u
t
u
t
a
a