2012-12-01/00561071 [SCR Power Controller TYA201]

65

5 Configuration

5.1.7

Binary output

This parameter specifies which control direction the binary output should have. It is
controlled by the multi-input interference signal.

v Chapter 8.1 "Binary signal for collective fault"
h

Switch to the configuration level

r

Binary output using the

key

Value/settings

Description

Control direction,
binary output

N/O contact

No fault message present:
14 and 15 pole and N/C contact closed or
13 and 15 optocoupler collector-emitter loop high-impedance

Fault message present:
13 and 15 pole and N/O contact closed or
13 and 15 optocoupler collector-emitter loop low-impedance

N/C contact

No fault message present:
13 and 15 pole and N/O contact closed or
13 and 15 optocoupler collector-emitter loop low-impedance

Fault message present:
14 and 15 pole and N/C contact closed or
13 and 15 optocoupler collector-emitter loop high-impedance