5 Configuration

68

2012-12-01/00561071 [SCR Power Controller TYA201]

5.2 Configuration example

Requirements

Load voltage 400 V

3 heating elements each with 1 kW connected in parallel

Load current: 3000 W/400 V = 7.5 A

Temperature coefficient TC = 1

Operating mode: phase angle control

Subordinate control loop: U

2

Base load: 0 %; maximum output level 100 %

Default setpoint value via standard signal of 0 to 20 mA.

These requirements are sufficient for the following power controllers:

Device type

709061/8-01-020-100-400-252