3 order details, Order details, 1 introduction – JUMO 709061 TYA 201 - Single-Phase Power Controller Operating Manual User Manual
Page 10
1 Introduction
8
2012-12-01/00561071 [SCR Power Switch TYA201]
1.3 Order details
The nameplate is affixed to the right-hand side of the case.
(1) Basic type
709061
TYA 201 single-phase SCR power controller
(2) Version
8
Standard with factory settings
9
Customer-specific programming according to specifications
(3) National language of display texts
01
German (set at factory)
02
English
03
French
(4) Load current
a
020
AC 20 A
032
AC 32 A
050
AC 50 A
100
AC 100 A
150
AC 150 A
200
AC 200 A
250
AC 250 A
(5) Subordinate control loop
100
U, U
2
010
I, I
2
(can be set to U, U
2
)
001
P (can be set to I, I
2
or U, U
2
)
(6) Load voltage
b
024
AC 24 V
-20 to +15 %, 45 to 63 Hz
042
AC 42 V
-20 to +15 %, 45 to 63 Hz
115
AC 115 V
-20 to +15 %, 45 to 63 Hz
230
AC 230 V
-20 to +15 %, 45 to 63 Hz
265
AC 265 V
-20 to +15 %, 45 to 63 Hz
400
AC 400 V
-20 to +15 %, 45 to 63 Hz
460
AC 460 V
-20 to +15 %, 45 to 63 Hz
500
AC 500 V
-20 to +15 %, 45 to 63 Hz
(7) Interface
00
None
54
RS485/422
64
PROFIBUS-DP
(8) Extra codes
252
Relay (changeover contact) 3 A
257
Optocoupler
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
/
-
-
-
-
-
/
Order code
709061
/
8
-
01
-
100
-
100
-
400
-
00
/
252
Order example
a
UL approval in preparation
b
Load voltage = voltage supply for control electronics
Important information:
Subordinate control loop U
2
, code 100: voltage control
Subordinate control loop I
2
, code 010: enables partial load failure detection, dual energy management, and current limiting
Subordinate control loop P, code 001: enables partial load failure detection, dual energy management, current limiting, free-running
economy circuit, and R control
At a load current of 250 A, observe voltage supply for fan!
v Chapter 3.2.5 "Type 709061/X-0X-250-XXX-XXX-XX-25X"