1 device data, 2 power controller, Device data – JUMO 709061 TYA 201 - Single-Phase Power Controller Operating Manual User Manual
Page 54: Power controller, Chapter 5.1.1 "device data, Chapter 5.1.2 "power control, 5 configuration
5 Configuration
52
2012-12-01/00561071 [SCR Power Controller TYA201]
5.1.1
Device data
Basic settings for display and temperature unit.
5.1.2
Power controller
Settings for the switching behavior of the power controller in the system.
Value/settings
Description
Temperature unit
°C
Defines the unit for the displayed temperatures, such as the
device temperature.
°F
Display contrast
0 to 50 to 100 %
Bright/dark contrast setting
Switch-off
display lighting
0000 to 1440 min
After the set number of minutes, the background lighting of
the display switches off. Power LED (green flashes).
0000 means: lighting is always switched on
Apply factory set-
tings
Apply now?
If the PGM key is pressed, the factory settings are restored.
k
/ bold = factory setting
Value/settings
Description
Mains switching
variant
Single-phase opera-
tion
v Chapter 3.3.1 "Single-phase operation: phase / N"
or
Chapter 3.3.2 "Single-phase operation: phase /
phase"
Free-running
economy circuit
Note:
-
Check for clockwise phasing
-
Only possible with P-control (code 001 in order code)
v Chapter 3.3.5 "Free-running economy circuit with
Economy circuit
master
One device is set as the MASTER and the other as the SLAVE.
This makes a three-phase current economy circuit possible.
v Chapter 3.3.6 "Master-slave three-phase current
v B 709062.0
Economy circuit
slave
SCR control
Continuous (power
controller)
The power controller provides the power for the load continu-
ously depending on the default setpoint value.
Logic (switch)
Note:
Subordinate control loop cannot be set!
The power controller acts like a switch and provides the power
by either switching ON or OFF.
k
/ bold = factory setting