beautypg.com

1 device data, 2 power controller, Device data – JUMO 709061 TYA 201 - Single-Phase Power Controller Operating Manual User Manual

Page 54: Power controller, Chapter 5.1.1 "device data, Chapter 5.1.2 "power control, 5 configuration

background image

5 Configuration

52

2012-12-01/00561071 [SCR Power Controller TYA201]

5.1.1

Device data

Basic settings for display and temperature unit.

5.1.2

Power controller

Settings for the switching behavior of the power controller in the system.

Value/settings

Description

Temperature unit

°C

Defines the unit for the displayed temperatures, such as the
device temperature.

°F

Display contrast

0 to 50 to 100 %

Bright/dark contrast setting

Switch-off

display lighting

0000 to 1440 min

After the set number of minutes, the background lighting of
the display switches off. Power LED (green flashes).

0000 means: lighting is always switched on

Apply factory set-
tings

Apply now?

If the PGM key is pressed, the factory settings are restored.

k

/ bold = factory setting

Value/settings

Description

Mains switching
variant

Single-phase opera-
tion

v Chapter 3.3.1 "Single-phase operation: phase / N"

or
Chapter 3.3.2 "Single-phase operation: phase /
phase"

Free-running
economy circuit

Note:

-

Check for clockwise phasing

-

Only possible with P-control (code 001 in order code)

v Chapter 3.3.5 "Free-running economy circuit with

purely resistive loads"

Economy circuit
master

One device is set as the MASTER and the other as the SLAVE.
This makes a three-phase current economy circuit possible.

v Chapter 3.3.6 "Master-slave three-phase current

economy circuit for resistive loads in star, delta con-
nection, or transformer loads (resistive-inductive)"

v B 709062.0

Economy circuit
slave

SCR control

Continuous (power
controller)

The power controller provides the power for the load continu-
ously depending on the default setpoint value.

Logic (switch)

Note:
Subordinate control loop cannot be set!

The power controller acts like a switch and provides the power
by either switching ON or OFF.

k

/ bold = factory setting