2 manual mode, 1 default setpoint value in manual mode, Manual mode – JUMO 709061 TYA 201 - Single-Phase Power Controller Operating Manual User Manual
Page 74: Default setpoint value in manual mode, For teach-in in manual mode), 6 special device functions
6 Special device functions
72
2012-12-01/00561071 [SCR Power Controller TYA201]
Teach-in
"Automatic (cy-
clically)"
"Automatically (cyclically)" means that the teach-in values are temporarily
saved again at intervals of 1 minute. This setting is particularly suitable for SIC
heating elements as in this case the resistance in the load point changes with
time due to aging.
When the power controller is disconnected from the supply voltage, the teach-
in values detected last are deleted and recalculated once voltage supply has
returned.
6.2 Manual mode
In this case, the setpoint value can be manually preset in % without the need
for external wiring via the analog input.
6.2.1 Default setpoint value in manual mode
Starting
Manual mode, as set ex works, can be accessed without entering a code.
h Press the
key once (selection menu)
h Press the
key again (manual mode)
h Use the
or
key to increase or decrease the setpoint value
The changes become effective immediately at the load output and are indicat-
ed on the display.
6.2.2 Configuring the teach-in (prerequisite for teach-in in manual mode)
The teach-in function records the current/voltage ratio of a load in the OK sta-
tus.
This function is not configured ex works.
v Configuration level See "Teach-in type load monitoring" on page 62.
Configuring
"manual"
teach-in
The power controller is in the "Measured value overview" level.
h Press the
key
h Config. level
r
Monitoring
r
Load monitoring
r
Undercurrent or overcur-
rent
r
Teach-in type load monit.
rS
"manual"
h Press the
key
II
h Press the
key twice
The device performs a reset.
H
The setpoint value for manual mode is not saved in the event of a pow-
er failure!
Load voltage
Load current
Setpoint value