6 binary inputs, Binary inputs, Chapter 5.1.6 "binary inputs – JUMO 709061 TYA 201 - Single-Phase Power Controller Operating Manual User Manual

Page 65: 5 configuration

background image

2012-12-01/00561071 [SCR Power Controller TYA201]

63

5 Configuration

5.1.6

Binary inputs

There are 2 binary inputs and one additional binary input for firing-pulse inhibit
available, to which a potential-free contact can be connected.
The following functions can be triggered with binary input 1 and 2:

h

Switch to the configuration level

r

Binary inputs using the

key

Value/settings

Description

Changeover, phase
angle control

Note:
The changeover to phase angle control mode is only possible
if the setting

r

Power controller

r

Operating mode

r

Burst-

firing mode has been made in the configuration level.

Switched off

No changeover

Binary input1

Changeover is controlled by binary input1

Binary input2

Changeover is controlled by binary input2

Ext. binary input1

Changeover is controlled via an interface

Ext. binary input2

Changeover is controlled via an interface

Ext. current limiting

Note:
This function can only be set if the following
presettings have been made:
Option 1:

Power controller

r

Operating mode

r

Phase angle control

and
Power controller

r

Current limiting

r

Yes

Option 2:

Power controller

r

Operating mode

r

Pulse groups

Power controller

r

Soft start

r

Yes

Power controller

r

Current limiting

r

Yes

If, for example, "Binary input 1" is set here, when the binary in-
put is closed, instead of the current limit value set under
"Power controller

r

Current limit value" coming into effect, the

"External current limit value" (further down in the table) be-
comes effective.

Switched off

No ext. current limiting

Binary input1

Ext. current limiting is controlled by binary input1

Binary input2

Ext. current limiting is controlled by binary input2

Ext. binary input1

Ext. current limiting is controlled via an interface

Ext. binary input2

Ext. current limiting is controlled via an interface

Ext. current limit
value

10 % to max. load
current of the
device
+10 %

Note:
This parameter is only available if a binary input is set for ext.
current limiting.
The max. load current varies depending on the device type.
For 20 A power controllers, 2 to 22 A can be set.

v Chapter 1.3 "Order details"

Key lock

Switched off

No key lock

Binary input1

Key lock is controlled by binary input1

Binary input2

Key lock is controlled by binary input2

Ext. binary input1

Key lock is controlled via an interface

Ext. binary input2

Key lock is controlled via an interface

k