5 Configuration
5.1.6
Binary inputs
There are 2 binary inputs and one additional binary input for firing-pulse inhibit
available, to which a potential-free contact can be connected.
The following functions can be triggered with binary input 1 and 2:
h
Switch to the configuration level
r
Binary inputs using the
key
Value/settings
Description
Changeover, phase
angle control
Note:
The changeover to phase angle control mode is only possible
if the setting
r
Power controller
r
Operating mode
r
Burst-
firing mode has been made in the configuration level.
Switched off
No changeover
Binary input1
Changeover is controlled by binary input1
Binary input2
Changeover is controlled by binary input2
Ext. binary input1
Changeover is controlled via an interface
Ext. binary input2
Changeover is controlled via an interface
Ext. current limiting
Note:
This function can only be set if the following
presettings have been made:
Option 1:
Power controller
r
Operating mode
r
Phase angle control
and
Power controller
r
Current limiting
r
Yes
Option 2:
Power controller
r
Operating mode
r
Pulse groups
Power controller
r
Soft start
r
Yes
Power controller
r
Current limiting
r
Yes
If, for example, "Binary input 1" is set here, when the binary in-
put is closed, instead of the current limit value set under
"Power controller
r
Current limit value" coming into effect, the
"External current limit value" (further down in the table) be-
comes effective.
Switched off
No ext. current limiting
Binary input1
Ext. current limiting is controlled by binary input1
Binary input2
Ext. current limiting is controlled by binary input2
Ext. binary input1
Ext. current limiting is controlled via an interface
Ext. binary input2
Ext. current limiting is controlled via an interface
Ext. current limit
value
10 % to max. load
current of the
device +10 %
Note:
This parameter is only available if a binary input is set for ext.
current limiting.
The max. load current varies depending on the device type.
For 20 A power controllers, 2 to 22 A can be set.
Key lock
Switched off
No key lock
Binary input1
Key lock is controlled by binary input1
Binary input2
Key lock is controlled by binary input2
Ext. binary input1
Key lock is controlled via an interface
Ext. binary input2
Key lock is controlled via an interface
k
/ bold = factory setting