6 Special device functions

6.1 Detection of load faults

The load monitoring function can detect and signal a load failure, partial load
failure, or a partial load short circuit.

Undercurrent

This function is used for one or more heating elements connected in parallel
that are to be monitored for breakage.

Overcurrent

This function is used for several heating elements connected in series that are
to be monitored for short circuits.

Function

This function does not only take the decreasing or increasing load current into
consideration but also includes the load voltage in the monitoring process.

The correct load ratios of the system are saved during teach-in.
Based on this status, the load changes are continuously monitored irrespec-
tive of the required output level. In the event of a breakage or short circuit of a
heating element, the load current increases or decreases. This is detected by
the load monitor and a load fault is signaled.

Limit value

A limit value must be entered in the configuration or operator level in % for the
load monitor. This limit value depends upon the number of heating elements
connected in parallel or in series.

For heating elements with a high positive or negative temperature coefficient,
a suitable limit value must be determined independently. The % value shown
below (see arrow) can be used as an aid for this.
This value represents the current deviation from the teach-in value. If the value
is > 0 %, the load has become more more high-resistance; if the value is <
0 %, it has become more low-resistance. This window can be accessed via
Operator level

r

Monitoring

r

Limit value load monit.

For heating elements with a temperature coefficient TC

1 the limit value can

be taken directly from the following tables:

Undercurrent

Number of
heating ele-
ments

Single-phase
operation

Star connection
with separate
star points without
neutral conductor

Star connection with
common star points
without neutral con-
ductor

Delta connection

5

10 %

-

-

4

13 %

10 %

-

3

17 %

13 %

10 %

2

25 %

20 %

12 %