6 connection object (05h) – INFICON Composer Elite Gas Concentration Monitor User Manual
Page 73
5 - 7
PN
07
4-
56
6-
P1
B
Composer Elite Operating Manual
5.4.1.6 Connection Object (05h)
Connection objects are shown in
The supported services are:
Class - Get Attribute Single (Revision, UINT, 0001h)
Instance - Get/Set Attribute Single
Table 5-6 Instance #1,#10...#14 (Explicit Messaging)
#
Name
Access
Type
Comments
1
State
Get
USINT
0 = Nonexistent
1 = Configuring
2 = Waiting for Connections ID
3 = Established
4 = Timeout
5 = Deferred Delete
2
Instance Type
Get
USINT
0000h (explicit messaging type)
3
Transport Class Trigger
Get
BYTE
83h (Server, Transport class 3)
4
Produced Connection ID
Get
UINT
-
5
Consumed Connection ID
Get
UINT
-
6
Initial Comm Characteristics
Get
BYTE
21 = Instance#1
33 = Instance #10..#14
7
Produced Connection Size
Get
UINT
262
8
Consumed Connection Size
Get
UINT
262
9
Expected Packet Rate
Get/Set(a)
UINT
2500ms
12
Watchdog Timeout Action
Get/Set(a)
USINT
0001h = Auto Delete (default)
0003h = Deferred delete
13
Produced Connection Path Length
Get
UINT
0000h (No connection path)
14
Produced Connection Path
Get
EPATH
-
15
Consumed Connection Path
Length
Get
UINT
0000h (no connection path)
16
Consumed Connection Path
Get
EPATH
-
17
Production Inhibit Time
Get
UINT
0000h
(a) Not able to be set on UCMM explicit message connections (Instance 10...14)