N o t e – ETC Unison DRd Dimming Rack Enclosure User Manual

Page 34

background image

30

DRd Enclosure Installation Manual

Step 5:

Strip the neutral wire to the length indicated in the table above and terminate to

the neutral terminal assembly. Torque to the recommended value also indicated

in the table above. For 230V AC DRd enclosures, the neutral bus is located on

the line input feed side of the enclosure.

Step 6:

Strip the ground/earth wires to the length indicated in the table above and

terminate to the ground bus terminal. Torque to the recommended value also
indicated in the table above.

N o t e :

Ground connections must use all metal nuts and lock washers.