100, 120, 127 v ac, 3ø drd enclosures, N o t e, L1 l2 l3 n – ETC Unison DRd Dimming Rack Enclosure User Manual
Page 30
26
DRd Enclosure Installation Manual
Step 3:
Tighten the lugs to the correct torque based on cable size. Torque ratings are
also labeled in the DRd enclosure for your convenience.
100, 120, 127 V AC, 3Ø DRd Enclosures
N o t e :
CE enclosures are supplied with ANSI hex wrenches for line feed terminations.
Type
DRd12
120 and 230V AC
DRd12
240 and 277V AC
DRd6
(all models)
Lug Mounting
Bolt Torque
6 Ft-lbs
8 Nm
11 Ft-lbs
15 Nm
6 Ft-lbs
8 Nm
Wire Range
350kcmil -
1 AWG
2-6 AWG
250kcmil -
1 AWG
2-6 AWG
2/0-3 AWG
4-6 AWG
185mm
2
-
50mm
2
35mm
2
-
16mm
2
120mm
2
-
50mm
2
35mm
2
-
16mm
2
70mm
2
-
25mm
2
25mm
2
-
16mm
2
Lug Wire
Tightening
Torque
375 in-lbs
200 in-lbs
375 in-lbs
275 in-lbs
50 in-lbs
45 in-lbs
42.4 Nm
22.6 Nm
42.4 Nm
31 Nm
5.65 Nm
5.1 Nm
C A U T I O N :
Dress wires neatly and avoid leaving extra wire inside the enclosure. Too much
clutter can restrict airflow and cause overtemp errors.
N o t e :
For 120V AC single phase installation you must modify the phase bus before
connecting wiring.