5

Install Rack Options

33

Step 4:

Loosen the terminal screws for as many wire pairs you are terminating. Keep in

mind that the connector is split into two segments when used with a Dual

Repeater Module. Be sure to terminate each wire pair to the correct segment.

Step 5:

Insert each white (typical) wire from the pairs into an “A” terminal on the

connector and tighten the screw firmly to secure the wire into the connector.

Step 6:

Insert each black (typical) wire from the pairs into an “B” terminal on the

connector and tighten the screw firmly to secure the wire into the connector.

Step 7:

The 14 AWG ground wire can terminate to the ground bus located inside the ERn

enclosure.

If grounded metal conduit is installed a ground wire may not be required for

termination. Reference the related

station installation manual

for details.

Step 8:

Replace the connector on the top right I/O board.

Terminate Auxiliary Power

Auxiliary power is required when you are installing powered Unison control stations. ETC

recommends using two 16 AWG (1.5mm

2

) stranded wires for 24 Vdc auxiliary power to the

control station(s). Auxiliary power is topology-free. Maximum auxiliary voltage runs are

dependant by the wire gauge and the distribution of auxiliary load determined by

installation. The auxiliary supply is capable is of powering up to four Paradigm Touchscreen

Stations and 28 interface stations.

The auxiliary power connector (labeled Aux Power) provides termination for up to 20 wires

in the ten position pluggable connector. Each terminal allows up to two 16 AWG(1.5mm

2

)

wire and provides 24 Vdc power to Unison control stations when used with the Paradigm

ACP.

Step 1:

Pull auxiliary control power wiring (typically 16 AWG (1.5mm

2

) red / black wire

pair) into the ERn enclosure through the conduit opening previously prepared.

Step 2:

Strip 3/16” (5mm) of insulation from the ends of each wire pair.

Step 3:

Remove the auxiliary power

connector from the right I/O board.

Step 4:

Loosen the terminal screws for as

many auxiliary wire pairs as you are

terminating.

Step 5:

Insert the black (typical) auxiliary

power wire from the pair into a “-”

terminal on the connector and

tighten the screw to secure the wire

into the connector.

Step 6:

Insert the red (typical) auxiliary power wire from the pair into a “+” terminal on the

connector and tighten the screw to secure the wire into the connector.

Step 7:

Repeat steps 5 and 6 for each auxiliary power wire in the enclosure.

Step 8:

Replace the connector on the right I/O board.

N o t e :

When utilizing a Paradigm Station Repeater Module (P-REP) or Paradigm Dual

Station Repeater Module (P-DREP) in an ERn4 rack, terminate the repeated LON

segment(s) and auxiliary power wiring to the top right I/O board.

- + - + - + - + - +