Install the rack enclosure – ETC Unison ERn Wall-mount Control Enclosure User Manual

Page 16

background image

12

Unison

®

ERn Wall Mount Enclosure Installation Manual

Install the Rack Enclosure

The wall must be strong enough to hold the rack fully populated with modules, conduit and

wire. The maximum weight of an ERn enclosure is approximately 45 lbs (20.4 kg).

Step 1:

Determine where your rack will be installed using the weight and dimension

requirements detailed in

“Where to Install the Enclosure,” page 8

.

Step 2:

Use the measured slot dimensions located in the graphic below to mark the hole

locations for the mounting hardware.

Step 3:

Drill the holes and install the mounting hardware for each rack.

• Four 3/8” (8-10mm) bolts or screws 2-4” (50-100mm) long, and suitable

wall plugs are suggested mounting hardware (lag bolts recommended).

• All hardware must support the weight of the rack unit fully populated with

modules.

• Expose at least 1” (25mm) of threads for mounting the rack.

Step 4:

Attach the rack enclosure to the mounting hardware using the mounting

keyholes.

Step 5:

Check that the rack is level and plumb then tighten the mounting hardware for a

secure installation.

ERn2 - 8.9” / 226mm

ERn4 - 14.2” / 360.7mm

5.5”

139.7mm

5.5”

139.7mm

4.5”

114.3mm

15.5”

393.7mm

ERn2 - 6.8” / 172.7mm

ERn4 - 12” / 304.8mm

3.4”

86.4mm

ERn enclosure rear panel