Final Installation and Power Up

25

Step 3:

Open the ERn door and check voltage between phase, neutral, and ground. The

ERn supports input power ranging + / - 10% of the rated voltage.

100 VAC, (acceptable range 90-110 VAC)

120 VAC, (acceptable range 108-132 VAC)

230 VAC CE, (acceptable range 207-253 VAC)

240 VAC, (acceptable range 216-264 VAC)

Step 4:

Turn off power at the main circuit breaker.

Final Installation

Step 1:

Install the Paradigm Architectural Control Processor (P-ACP) in the appropriate

module slot.

Step 2:

Install the Paradigm Station Power Module (P-SPM) in the module slot above the

Paradigm Architectural Control Processor.

Step 3:

Install option modules if they are not installed. For an ERn4, you may install

either two blank modules, a Paradigm Dual Repeater Module (P-DREP) in the

top two module slots of the enclosure, or only a Paradigm Station Repeater

module (P-REP) in the top module slot with a blank module below.

Step 4:

Install either the ERn blank option module, the ERn ethernet switch Module

(ERn-NET), or the Redundant Power Supply (ERn-RPS) in the lower option

module slot.
a: If installing the ERn ethernet switch Module (ERn-NET) or the Redundant

Rack Power Supply (ERn-RPS) module in the option module slot, be certain

you have completed the installation requirements.

See “Install Rack Options”

on page 26.

Step 5:

Install blank module (ERn-BM) in any unused module slot in the enclosure to

maintain the required convection cooling requirements.

N o t e :

Neither the Redundant Power Supply (ERn-RPS) nor the Ethernet Switch module

(ERn-NET) are supported in an ERn4 enclosure at 230 VAC. Instead, an ERn4 at

230 VAC is shipped from the factory with a rack power supply installed in the top

(normal) position and in the lower option module slot as standard.