Connect control wiring – ETC Unison ERn Wall-mount Control Enclosure User Manual

Page 21

background image

3

Terminate Wiring

17

Connect Control Wiring

Low voltage data connects to pluggable connectors on the left and right input/output boards

of the ERn enclosure. The ERn2 includes only one each left and right I/O board while the

ERn4 includes two of each.

The left I/O provides termination for contact inputs and outputs, RS-232 serial, and
Ethernet control.

The right I/O provides termination for LinkPower, auxiliary power, DMX in, DMX Out,
DMX through, and all enclosure option kits. The right I/O also provides termination for
option modules installed on the bottom module slot of the rack enclosure for enhanced
control and operation.

N o t e :

All low voltage control cables must be run in separate conduit from power wires in

accordance with local codes.

W A R N I N G :

RISK OF DEATH BY ELECTRIC SHOCK! Failure to disconnect all power to

the rack before working in the enclosure could result in serious injury or

even death.

Right I/O boards

Left I/O board(s)

Wire tie down locations

are provided on the rear

panel.