8. Select the desired Trigger bits.
Trigger bits represent the eight possible communication module sta-
tus events that can be monitored by the relay module.
Com 1/Com 2 —
Communication fault.
Sensor Fault —
Includes improperly wired sensor, sensor
input below the threshold for normal
operation, or invalid configuration.
In Calibration —
Calibration in progress.
High/Low Alarm —
Alarm condition.
Digital Input —
Communication module’s digital input
active.
Output Relay —
Communication module’s relay is active.
9. Select the desired I/O conditions in the Input/Output box.
Relay Energize. Check this box if a normally energized relay coil
is desired. The coil will become de-energized when the status of the
device becomes active.
Latching. When Start/End mode is selected, the output relay is
always latching. If List mode is selected, check this box if latching
relay operation is desired.
Invert Input. The normal status for the inputs is 0 with the input
open (active status is 1 with input closed). This option is provided to
allow for the use of a normally closed input.
10.If List Mode is selected, enter in the “Voting” box the number of
detectors within the group that must register an active Trigger Bit for
the Relay Node to actuate.
11.Enter the desired update rate.
12.Click on Accept. Click on Close to exit and return to the Point
Configuration screen, or use the scroll arrows to select the next point
for configuration.