beautypg.com

Det-Tronics EagleVision - PC User Manual

Page 12

background image

interval. When 250 LON devices are used, the average status update
time can be set for 5 seconds. Note that all units do not need to be pro-
grammed for the same update rate. Higher priority devices can be set
for a shorter time, while lower priority units can be set for a longer time.
The important factor is the average time for the entire LON — this must
not exceed 50 messages per second.

The color of the tab in the lower left hand corner of the Point
Configuration screen indicates the current system status.

None = Normal operation (No devices in Alarm or Fault)
Red = Alarm
Yellow = Fault.

From the Point Configuration screen, click on the Overview button to dis-
play the System Overview screen. See Figure III-1. This screen provides
an overview of the entire system. Each configured node is represented
by a square on the loop, and is identified by its address number. The
color of the square indicates the status condition. (This screen is also
used for diagnostics purposes. Refer to Section IX - LON Troubleshooting
for details.)

Black = Normal operation
Red = Alarm
Yellow = Fault condition.

NOTE

An alarm condition will override a fault condition.

95-8479

3.3

C

ONFIGURATION AND

S

YSTEM

M

ONITORING

O

VERVIEW

S

YSTEM

M

ONITORING

FIGURE III-1

System Overview

Screen