beautypg.com

Caution – Bryant Bruant 4 Way Gas 355AAV User Manual

Page 21

background image

21

Manufacturer’s Coil Assembly or when Manufacturer’s Coil Box is
used.

1. Determine application being installed from Table 3.
2. Construct hole in floor per dimensions specified in Table 3

and Fig. 22.

3. Construct plenum to dimensions specified in Table 3 and

Fig. 22.

4. If downflow subbase is used, install as shown in Fig. 23.
5. If coil assembly is used, install as shown in Fig. 24.

NOTE: Remove furnace perforated discharge duct flanges when
they interfere with mating flanges on coil on downflow subbase.
To remove furnace perforated discharge duct flange, use hand
seamers, wide duct pliers or duct flange tool to bend flange back
and forth until it breaks off. Be careful of sharp edges. (See Fig.
25.)

UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit

operation or performance satisfaction.
Do not bend duct flanges inward as shown in Fig. 25. This

will affect airflow across heat exchangers and may cause limit

cycling or premature heat exchanger failure. Remove duct

flange completely or bend it inward a minimum of 210_ as

shown in Fig. 25.

CAUTION

!

Step 3 — Installation in Horizontal Applications

These furnaces can be installed in either horizontal left or right

discharge position. In a crawlspace, furnace can either be hung
from floor joist or installed on suitable blocks or pad. Furnace can

be suspended from each corner by hanger bolts and angle iron
supports. (See Fig. 26.) Cut hanger bolts (4 each 3/8--in. (10 mm)

all--thread rod) to desired length. Use 1 X 3/8--in. (10 mm) flat

washers, 3/8--in. (10 mm) lock washers, and 3/8--in. (10 mm) nuts
on hanger rods as shown in Fig. 26. Dimples are provided for hole

locations. (See Fig. 2.)

UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit

operation or performance satisfaction.
The entire length of furnace MUST be supported when

furnace is used in a horizontal position to ensure proper

draining. When suspended, bottom brace supports sides and

center blower shelf. When unit is supported from the ground,

blocks or pad should support sides and center blower shelf

area.

CAUTION

!

Step 4 — Air Ducts
GENERAL REQUIREMENTS

The duct system should be designed and sized according to

accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and

Air Conditioning Contractors National Association (SMACNA) or
American Society of Heating, Refrigerating and Air Conditioning

Engineers (ASHRAE) or consult The Air Systems Design

Guidelines reference tables available from your local distributor.
The duct system should be sized to handle the required system

design CFM at the design static pressure.
When a furnace is installed so that the supply ducts carry air

circulated by the furnace to areas outside the space containing the

furnace, the return air must also be handled by a duct(s) sealed to
the furnace casing and terminating outside the space containing the

furnace.
Secure ductwork with proper fasteners for type of ductwork used.

Seal supply-- and return--duct connections to furnace with code

approved tape or duct sealer.
Flexible connections should be used between ductwork and

furnace to prevent transmission of vibration. Ductwork passing
through unconditioned space should be insulated to enhance

system performance. When air conditioning is used, a vapor barrier

is recommended.
Maintain a 1--in. (25 mm) clearance from combustible materials to

supply air ductwork for a distance of 36 in. (914 mm) horizontally
from the furnace. See NFPA 90B or local code for further

requirements.
For a furnace not equipped with a cooling coil, the outlet duct shall
be provided with a removable access panel. This opening shall be

accessible when the furnace is installed and shall be of such a size
that the heat exchanger can be viewed for possible openings using

light assistance or a probe can be inserted for sampling the air
stream. The cover attachment shall prevent leaks.

DUCTWORK ACOUSTICAL TREATMENT

Metal duct systems that do not have a 90 degree elbow and 10 ft.

(3.0 M) of main duct to the first branch take--off may require
internal acoustical lining. As an alternative, fibrous ductwork may

be used if constructed and installed in accordance with the latest
edition of SMACNA construction standard on fibrous glass ducts.

Both acoustical lining and fibrous ductwork shall comply with

NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air
ducts.

SUPPLY AIR CONNECTIONS

Upflow Furnaces

Connect supply--air duct to 3/4--in. (19.1 mm) flange on furnace

supply--air outlet. The supply--air duct attachment must ONLY be
connected to furnace supply--/outlet--air duct flanges or air

conditioning coil casing (when used). DO NOT cut main furnace
casing to attach supply side air duct, humidifier, or other

accessories. All accessories MUST be connected external to

furnace main casing.

Downflow Furnaces

Connect supply--air duct to supply--air opening on furnace. The

supply--air duct attachment must ONLY be connected to furnace

supply/outlet or air conditioning coil casing (when used), when
installed on non--combustible material. When installed on

combustible material, supply--air duct attachment must ONLY be
connected to an accessory subbase or factory approved air

conditioning coil casing. DO NOT cut main furnace casing to
attach supply side air duct, humidifier, or other accessories. All

accessories MUST be connected external to furnace main casing.

Supply air opening duct flanges must be modified per Fig. 25.

Horizontal Furnaces

Connect supply--air duct to supply air opening on furnace. The

supply--air duct attachment must ONLY be connected to furnace

supply/outlet or air conditioning coil casing (when used). DO NOT
cut main furnace casing to attach supply side air duct, humidifier,

or other accessories. All accessories MUST be connected external
to furnace main casing.

355A