FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in fire, property

damage, personal injury, or death.
Do NOT install furnace on its back. (See Fig. 16.) Safety

control operation will be adversely affected. Never connect

return--air ducts to back of furnace.

!

WARNING

UNIT DAMAGE HAZARD
This gas furnace may be used for construction heat provided

that:
--The furnace is permanently installed with all electrical

wiring, piping, air filters, venting and ducting installed

according to these installation instructions. A return air duct is

provided, sealed to the furnace casing, and terminated outside

the space containing the furnace. This prevents a negative

pressure condition as created by the circulating air blower,

causing a flame rollout and/or drawing combustion products

into the structure.

--The furnace is controlled by a thermostat. It may not be “hot

wired” to provide heat continuously to the structure without

thermostatic control.

--Clean outside air is provided for combustion. This is to

minimize the corrosive effects of adhesives, sealers and other

construction materials. It also prevents the entrainment of

drywall dust into combustion air, which can cause fouling and

plugging of furnace components.

--The temperature of the return air to the furnace is maintained

between 55_F (13_C) and 80_F (27_C), with no evening

setback or shutdown. The use of the furnace while the

structure is under construction is deemed to be intermittent

operation per our installation instructions.

--The air temperature rise is within the rated rise range on the

furnace rating plate, and the firing rate has been set to the

nameplate value.

--The filters used to clean the circulating air during the

construction process must be either changed or thoroughly

cleaned prior to occupancy.

--The furnace, ductwork and filters are cleaned as necessary to

remove drywall dust and construction debris from all HVAC

system components after construction is completed.

--After construction is complete, verify furnace operating

conditions including ignition, input rate, temperature rise and

venting, according to the manufacturer’s instructions.

CAUTION

!

The furnace and its return air system shall be designed and installed
so that negative pressure created by the air circulating fan cannot

affect another appliance’s combustion air supply or act to mix
products of combustion with circulating air, and that the air

circulating fan of the furnace, if installed in an enclosure

communicating with another fuel--burning appliance not of the
direct--vent type, shall be operable only when any door or panel

covering an opening in the furnace fan compartment or in a return
air plenum on ducts is in the closed position.

UNIT DAMAGE HAZARD
Failure to follow this caution may result in minor property or

unit damage.
If these furnaces are installed in an unconditioned space where

ambient temperatures may be 32_F (0_C) or lower, freeze

protection measures must be taken. (See Fig. 17.)

CAUTION

!

FRONT

BACK

FRONT

B

A

C

K

A93043

Fig. 16 -- Prohibit Installation on Back

A07911

Fig. 17 -- Freeze Protection

Step 2 — Low--Heat Only Installation

This 355AAV furnace can be installed to operate in the low--heat

only heating mode when sized using the low--heat heating capacity.

This is accomplished by placing setup switch SW1--2 in the ON
position to provide only low--heat operation. See Fig. 37 and Table

13. With this setup, high--heat operation will not occur.

355A