beautypg.com

Bryant Bruant 4 Way Gas 355AAV User Manual

Page 13

background image

13

VENT

MANUAL

SHUTOFF

GAS VALVE

SEDIMENT
TRAP

CONDENSATE
TRAP

DRAIN

ACCESS OPENING
FOR TRAP

30-IN. (762mm) MIN
WORK AREA

A 12-IN. (305mm) MIN HORIZONTAL PIPE
SECTION IS RECOMMENDED WITH
SHORT (5 TO 8 FT / 1.5 TO 2.4M) VENT
SYSTEMS TO REDUCE EXCESSIVE
CONDENSATE DROPLETS FROM
EXITING THE VENT PIPE.

A 3-IN.(76mm) MINIMUM CLEARANCE
TO COMBUSTION-AIR INTAKE
IS REQUIRED.

5

3

/

4

IN. (146mm)

NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE

FURNACE AND CONDENSATE TRAP WHEN A CONDENSING
FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.

COMBUSTION AIR

INTAKE

A96184

Fig. 13 -- Attic Location and Working Platform for Non--Direct Vent (1--Pipe) Applications -- Sizes 040 through 120 Only

c. Route extended tube (blue label) to condensate trap and

cut to appropriate length.

d. Clamp tube to prevent any condensate leakage.

2. Inducer Housing Drain Tube

a. Remove and discard LOWER (molded) inducer housing

drain tube which was previously connected to
condensate trap.

b. Use inducer housing drain extension tube (violet label

and factory--supplied in loose parts bag) to connect
LOWER inducer housing drain connection to

condensate trap.

c. Determine appropriate length, cut, and connect tube.

d. Clamp tube to prevent any condensate leakage.

3. Relief Port Tube

a. Extend collector box tube (green label) which was

previously connected to condensate trap by splicing to
small diameter tube (factory--supplied in loose parts

bag).

b. Route extended collector box pressure tube to relief port

connection on condensate trap.

c. Determine appropriate length, cut, and connect tube.

d. Clamp tube to prevent any condensate leakage.

Condensate Trap Field Drain Attachment

Refer to Condensate Drain section for recommendations and

procedures.

Pressure Switch Tubing

The LOWER collector box pressure tube (pink label) is factory

connected to the High Pressure Switch for use when furnace is
installed in UPFLOW applications. This tube MUST be

disconnected, extended, rerouted, and then reconnected to the
pressure switch in HORIZONTAL LEFT applications for 060 and

080 heating input furnaces.
NOTE: See Fig. 11 or tube routing label on main furnace door to
check for proper connections.
Modify tube as described below.

1. Disconnect collector box pressure tube (pink label) attached

to High Pressure Switch.

2. Use smaller diameter tube (factory--supplied in loose parts

bag) to extend tube disconnected in item 1.

3. Route extended tube:

a. Behind inducer housing.

b. Between blower shelf and inducer housing.

4. Determine appropriate length, cut, and reconnect tube to

High Pressure Switch connection labeled COLLECTOR
BOX.

Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommendations

and procedures.

Construct a Working Platform

Construct working platform where all required furnace clearances

are met. (See Fig. 3 and 12 or 13.)

355A