Caution, Warning – Bryant Bruant 4 Way Gas 355AAV User Manual
Page 14
![background image](/manuals/52629/14/background.png)
14
PLUG
COLLECTOR BOX DRAIN TUBE
(BLUE AND WHITE STRIPED)
INDUCER HOUSING
DRAIN TUBE (VIOLET)
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR BOX TUBE (GREEN)
CAP
COLLECTOR BOX DRAIN TUBE (BLUE)
COLLECTOR BOX TUBE (PINK)
AUXILIARY "J" BOX RELOCATED HERE
CONDENSATE
TRAP
A02289
Fig. 14 -- Horizontal Right Tube Configuration
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit
operation.
The condensate trap MUST be installed below furnace. See
Fig. 6 for dimensions. The drain connection to condensate trap
must also be properly sloped to an open drain.
CAUTION
!
NOTE: A 12--in. (305 mm) minimum offset pipe section is
recommended with short (5 to 8 ft./ 1.5 -- 2.4 M) vent systems.
This recommendation is to reduce excessive condensate droplets
from exiting the vent pipe. (See Fig. 12, 13 or 42.)
Step 5 — Horizontal Right (Supply--Air
Discharge) Applications
A horizontal right furnace application is where furnace blower is
located to the left of combustion and controls section of furnace,
and conditioned air is discharged to the right.
MINOR PROPERTY DAMAGE
Failure to follow this caution may result in minor property
damage.
Local codes may require a drain pan under entire furnace and
condensate trap when a condensing furnace is used in attic
application or over a finished ceiling.
CAUTION
!
NOTE: In Canada, installations shall be in accordance with
current NSCNGPIC Installation Codes and/or local codes.
NOTE: The auxiliary junction box (J--box) MUST be relocated to
opposite side of furnace casing. (See Fig. 13.) See Electrical
Connection section for J--box relocation.
Condensate Trap Location
The condensate trap must be removed from the factory--installed
blower shelf location and relocated in selected application location
as shown in Fig. 2 or 14.
To relocate condensate trap from the blower shelf to desired
location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs
inward and rotating trap.
3. Install casing hole filler cap (factory--supplied in loose parts
bag) into blower shelf hole where trap was removed.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury
or death.
Casing hole filler cap must be installed in blower shelf hole
when condensate trap is relocated to prevent combustion
products being drawn in from appliances in the equipment
room.
!
WARNING
4. Install condensate trap into right--hand side casing hole by
inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler
caps (factory--supplied in loose parts bag).
Condensate Trap Tubing
NOTE: See Fig. 14 or tube routing label on main furnace door to
check for proper connections.
355A