beautypg.com

Caution, Warning – Bryant Bruant 4 Way Gas 355AAV User Manual

Page 12

background image

12

COMBUSTION - AIR

INTAKE

VENT

MANUAL

SHUTOFF

GAS VALVE

SEDIMENT
TRAP

CONDENSATE
TRAP

DRAIN

ACCESS OPENING
FOR TRAP

30

(762 mm)MIN

WORK AREA

A 12-IN. (305 mm) MIN HORIZONTAL PIPE
SECTION IS RECOMMENDED WITH
SHORT (5 TO 8 FT / 1.5 TO 2.4 M) VENT
SYSTEMS TO REDUCE EXCESSIVE
CONDENSATE DROPLETS FROM
EXITING THE VENT PIPE.

5

3

/

4

(146 mm)

NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE

FURNACE AND CONDENSATE TRAP WHEN A CONDENSING
FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.

A93031

Fig. 12 -- Attic Location and Working Platform for Direct Vent (2--Pipe) Application -- All Sizes

Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommendations

and procedures.

Step 4 — Horizontal Left (Supply--Air Discharge)

Applications

A horizontal left furnace application is where furnace blower is

located to the right of combustion and controls section of furnace,
and conditioned air is discharged to the left.

MINOR PROPERTY HAZARD
Failure to follow this caution may result in minor property

damage.
Local codes may require a drain pan under entire furnace and

condensate trap when a condensing furnace is used in an attic

application or over a finished ceiling.

CAUTION

!

NOTE: In Canada, installations shall be in accordance with
current NSCNGPIC and/or local codes.

Condensate Trap Location

The condensate trap must be removed from the factory--installed

blower shelf location and relocated in selected application location

as shown in Fig. 2 or 11.
To relocate condensate trap from the blower shelf to desired

location, perform the following:

1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs

inward and rotating trap.

3. Remove casing hole filler cap from casing hole. (See Fig. 2

or 11.)

4. Install casing hole filler cap (factory--supplied in loose parts

bag) into blower shelf hole where trap was removed.

CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury

or death.
Casing hole filler cap must be installed in blower shelf hole

when condensate trap is relocated to prevent combustion

products being drawn in from appliances in the equipment

room.

!

WARNING

5. Install condensate trap into left--hand side casing hole by

inserting tube connection stubs through casing hole and

rotating until tabs snap into locking position.

6. Fill unused condensate trap casing holes with plastic filler

caps (factory--supplied in loose parts bag).

Condensate Trap Tubing

NOTE: See Fig. 11 or tube routing label on main furnace door to
check for proper connections.

1. Collector Box Drain Tube

a. Install drain tube coupling (factory--supplied in loose

parts bag) into collector box drain tube (blue label)
which was previously connected to condensate trap.

b. Connect large diameter drain tube and clamp

(factorysupplied in loose parts bag) to drain tube
coupling, extending collector box drain tube.

355A