Horner APG QX751 OCS User Manual
Page 45
MAN0890-02-EN CH. 9
August 20, 2009
Page 45 of 96
ECN # 979
View I/O Slots
If BPxx is not installed, the View I/O Slots Sub-Menu displays 4 System Settings, none of which are
editable. If BPxx is installed, the View I/O Slots Sub-Menu displays 6 System Settings, only one of which
is editable.
QX:
Slot 1:+ I/O: ETN300
= ETN300 has not been configured through Cscape
OR
Slot 1: I/O: ETN300
= ETN300 has been configured through Cscape
Slot 2: I/O: Empty
= N/A on this platform
Slot 3: I/O: Empty
= N/A on this platform
Slot 4: I/O: Empty
= N/A on this platform
QX751/BPxx:
Base Selected:
CPU
= I/O on this base is fixed depending on installed BPxx
Main
= Refers to the I/O installed on the BPxx
2-6
= Refers to the I/O installed on remote FOX hubs/bases
Base Online?
Yes
= Indicates no problems with fiber cables
No
= Indicates a problem with fiber cables
Slot x:+ I/O: ABCxyz
= I/O module is installed but not configured
Slot x:- I/O: Missing
= I/O module is configured but not installed
Slot x:? I/O: ABCxyz
= I/O module installed but another I/O module configured
Slot x: I/O: ABCxyz
= I/O module is installed and configured properly
View I/O Slots Examples
QX751BP43:
QX751BP41:
Base Selected:
CPU
Base Selected:
CPU
Base Online?
Yes
Base Online?
Yes
Slot 1: I/O: FOX100
Slot 1: I/O: FOX100
Slot 2: I/O: ETN300
Slot 2: I/O: ETN300
Slot 3: I/O: HSC501
Slot 3: I/O: Empty
Slot 4: I/O: Empty
Slot 4: I/O: Empty
QX751BP43:
QX751BP41:
Base Selected:
Main
Base Selected:
Main
Base Online?
Yes
Base Online?
Yes
Slot 1: I/O: ASC100
Slot 1: I/O: THM100
Slot 2: I/O: DQM902
Slot 2: I/O: MIX901
Slot 3: I/O: MIX111
Slot 4: I/O: DIQ712
QX751/BPxx: QX751/BPxx:
Base Selected:
5
Base Selected:
4
Base Online?
Yes
Base Online?
No
Slot 1:? I/O: DIQ624
Slot 1:- I/O: Missing
Slot 2: I/O: RTD100
Slot 2:- I/O: Missing
Slot 3:+ I/O: MIX902
Slot 3: I/O: Empty
Slot 4:- I/O: Missing
Slot 4: I/O: Empty