beautypg.com

Horner APG QX751 OCS User Manual

Page 44

background image

CH.9

MAN0890-02-EN

August 20, 2009

Page 44 of 96

ECN # 979

Fault

= One or more power-on self-tests failed



View OCS Diags

The View OCS Diags Sub-Menu displays up to 10 System Diagnostics, all of which are not editable. The
Net Errors, Network State, Network ID and Dup Net ID System Diagnostics only appear for QX751
models that have a BPxx attached.

The first two System Diagnostics are critical. If any of them indicate a Fault condition, the QX751will not
enter or remain in Run mode, and the problem must be investigated and corrected.

Logic Error:

Ok

= All executed ladder instructions are legal for loaded

firmware

Fault

= A ladder instruction not supported by firmware was

found


User Program:

Ok

= Ladder program and I/O configuration loaded

successfully

Fault

= Ladder program or I/O configuration not loaded or load

failed

The last nine System Diagnostics are informational. If any of them indicate a Warning condition, the
QX751can still enter and remain in Run mode, but the problem should be investigated and corrected.

User Graphics: Ok

=

Application

graphics

objects loaded successfully

Warning

= Application graphics objects not loaded or load failed

W-Dog Trips:

0

= Watchdog timer has not tripped since the last power-up

x

= Number of times watchdog timer has tripped


Net Errors:

0

= No CAN network bus-off errors have occurred

x

= Number of CAN network bus-off errors that have occurred


Network State:

Ok

= At least one other node was found on the CAN network

Warning

= No other nodes were found on the CAN network


Network ID:

Ok

= This node’s CAN Network ID was in the range 1 to 253

Warning

= This node’s CAN Network ID was out of range at power-up


Dup Net ID:

Ok

= This node’s Network ID is unique on the CAN network

Warning

= This node’s Network ID is duplicated in another node


Clock Error:

Ok

= Time and date have been set

Warning

= Time and date need to be set


I/O System:

Ok

= I/O configuration matches the installed I/O and COM

modules

Warning

= I/O configuration needs updating to match installed

Modules


Battery:

Ok

= Battery voltage level at an acceptable level

Warning

= Battery voltage level below an acceptable level