Second analog input calibration (2cal) 86, Second analog input (remote setpoint) 86, Heater current monitor 86 – Red Lion TCU User Manual
Page 94: Motorized valve positioner 86
Analog Output Calibration (ANCL) (Cont’d)
0 to 10 VDC
Press PAR until ANCL appears in the display. Connect a precision
voltmeter (0.1% accuracy) to rear terminals (+) #11 and (-) #12.
Display
Parameter
Description/Comments
ANC1
Analog output 0 VDC
code value
Observe voltage reading. If 0.00 VDC,
press PAR. If not equal, modify existing
code value using up and down buttons to
achieve 0.00 VDC. Press PAR.
ANC2
Analog output 10
VDC code value
Observe voltage reading. If 10.00 VDC,
Press PAR. If not equal, modify existing
code value using up and down buttons to
achieve 10.00 VDC. Press PAR.
Second Analog Input Calibration (2CAL)
The signals applied to the Second analog Input for calibration depend on
the type of model. Second Analog Input, Heater Current Monitor, and
Motorized Valve Positioner represent the models for which unique
calibration signals are required.
Second Analog Input (Remote Setpoint)
Connect precision DC milliampere source (0.01% accuracy) to rear
terminals labeled Second Analog Input, 4-20 mA+ and 4-20 mA-.
Display
Parameter
Description/Comments
StP1
0.00 mA step
Apply 0.00 mA DC, press PAR.
StP2
5.00 mA step
Apply 5.00 mA DC, press PAR.
StP3
10.00 mA step
Apply 10.00 mA DC, press PAR.
StP4
15.00 mA step
Apply 15.00 mA DC, press PAR.
StP5
20.00 mA step
Apply 20.00 mA DC, press PAR.
Heater Current Monitor
Connect precision AC milliampere source (0.1% accuracy) to rear
terminals labeled Second Analog Input, CT+ And CT-.
Display
Parameter
Description/Comments
StP1
0.0 mA step
Apply 0.0 mA AC 60 Hz, press PAR.
StP2
25.0 mA step
Apply 25.0 mA AC 60 Hz, press PAR.
StP3
50.0 mA step
Apply 50.0 mA AC 60 Hz, press PAR.
StP4
75.0 mA step
Apply 75.0 mA AC 60 Hz, press PAR.
StP5
100.0 mA step
Apply 100.0 mA AC 60 Hz, press PAR.
Motorized Valve Positioner
Construct a precision resistor
divider network consisting of four
250
W 0.1% tolerance resistors
connected in series as shown in
F i g u r e 4 5 , R e s i s t o r D i v i d e r .
Connect one end of the resistor
string to the rear terminal labeled
S l i d e w i r e F e e d b a c k I n p u t s ,
C o mm. a n d t h e o t h e r e n d t o
Excitation. The connection to the
W i p e r t e r mi n a l c o me s f r o m
different points of the resistor
string.
Display
Parameter
Description/Comments
StP1
0.0% step
Connect wiper input to 0% point of divider
(Comm.), wait 10 seconds, press PAR.
StP2
25.0% step
Connect wiper input to 25% point of divider,
wait 10 seconds, press PAR.
StP3
50.0% step
Connect wiper input to 50% point of divider,
wait 10 seconds, press PAR.
StP4
75.0% step
Connect wiper input to 75% point of divider,
wait 10 seconds, press PAR.
StP5
100.0% step
Connect wiper input to 100% point of divider
(Excitation), wait 10 seconds press PAR.
86
Figure 45, Resistor Divider