Analog Output Calibration (ANCL) (Cont’d)

0 to 10 VDC

Press PAR until ANCL appears in the display. Connect a precision

voltmeter (0.1% accuracy) to rear terminals (+) #11 and (-) #12.

Display

Parameter

Description/Comments

ANC1

Analog output 0 VDC
code value

Observe voltage reading. If 0.00 VDC,
press PAR. If not equal, modify existing
code value using up and down buttons to
achieve 0.00 VDC. Press PAR.

ANC2

Analog output 10
VDC code value

Observe voltage reading. If 10.00 VDC,
Press PAR. If not equal, modify existing
code value using up and down buttons to
achieve 10.00 VDC. Press PAR.

Second Analog Input Calibration (2CAL)

The signals applied to the Second analog Input for calibration depend on

the type of model. Second Analog Input, Heater Current Monitor, and
Motorized Valve Positioner represent the models for which unique
calibration signals are required.

Second Analog Input (Remote Setpoint)

Connect precision DC milliampere source (0.01% accuracy) to rear

terminals labeled Second Analog Input, 4-20 mA+ and 4-20 mA-.

Display

Parameter

Description/Comments

StP1

0.00 mA step

Apply 0.00 mA DC, press PAR.

StP2

5.00 mA step

Apply 5.00 mA DC, press PAR.

StP3

10.00 mA step

Apply 10.00 mA DC, press PAR.

StP4

15.00 mA step

Apply 15.00 mA DC, press PAR.

StP5

20.00 mA step

Apply 20.00 mA DC, press PAR.

Heater Current Monitor

Connect precision AC milliampere source (0.1% accuracy) to rear

terminals labeled Second Analog Input, CT+ And CT-.

Display

Parameter

Description/Comments

StP1

0.0 mA step

Apply 0.0 mA AC 60 Hz, press PAR.

StP2

25.0 mA step

Apply 25.0 mA AC 60 Hz, press PAR.

StP3

50.0 mA step

Apply 50.0 mA AC 60 Hz, press PAR.

StP4

75.0 mA step

Apply 75.0 mA AC 60 Hz, press PAR.

StP5

100.0 mA step

Apply 100.0 mA AC 60 Hz, press PAR.

Motorized Valve Positioner

Construct a precision resistor

divider network consisting of four
250

W 0.1% tolerance resistors

connected in series as shown in
F i g u r e 4 5 , R e s i s t o r D i v i d e r .
Connect one end of the resistor
string to the rear terminal labeled
S l i d e w i r e F e e d b a c k I n p u t s ,
C o mm. a n d t h e o t h e r e n d t o
Excitation. The connection to the
W i p e r t e r mi n a l c o me s f r o m
different points of the resistor
string.

Display

Parameter

Description/Comments

StP1

0.0% step

Connect wiper input to 0% point of divider
(Comm.), wait 10 seconds, press PAR.

StP2

25.0% step

Connect wiper input to 25% point of divider,
wait 10 seconds, press PAR.

StP3

50.0% step

Connect wiper input to 50% point of divider,
wait 10 seconds, press PAR.

StP4

75.0% step

Connect wiper input to 75% point of divider,
wait 10 seconds, press PAR.

StP5

100.0% step

Connect wiper input to 100% point of divider
(Excitation), wait 10 seconds press PAR.

86

Figure 45, Resistor Divider