Red Lion TCU User Manual
Page 83
9.
OUTPUT MODULES [Optional] (For All Output Channels)
:
Relay
:
Type
: Form-C (Form-A with some models. See Ordering Information)
Rating
: 5 Amps @ 120/240 VAC or 28 VDC
(resistive load
), 1/8 HP @
120 VAC
(inductive load)
Life Expectancy
: 100,000 cycles at maximum load rating.
(Decreasing
load and/or increasing cycle time, increases life expectancy).
Logic/SSR Drive
: Can drive multiple SSR Power Units.
Type
: Non-isolated switched DC, 12 VDC typical
Drive
: 45 mA maximum
Triac
:
Type
: Isolated, Zero Crossing Detection
Rating
:
Voltage
: 120/240 VAC
Max. Load Current
: 1 Amp @ 35°C
0.75 Amp @ 50°C
Min. Load Current
: 10 mA max.
Offstate Leakage Current
: 7 mA max. @ 60 Hz
Operating Frequency
: 20 to 400 Hz
Protection
: Internal Transient Snubber, Fused
10.
MAIN CONTROL OUTPUT (Heating or Cooling)
:
Control
: PID or ON/OFF
Output
: Time proportioning or linear DC
Hardware
: Plug-in, replaceable output modules
Cycle time
: Programmable
Auto-tune
: When selected, sets proportional band, integral time,
and derivative time values.
Probe Break Action
: Programmable
11.
COOLING OUTPUT (Optional)
:
Control
: PID or ON/OFF
Output
: Time proportioning or linear DC
Hardware
: Plug-in, replaceable output modules
Cycle time
: Programmable
Proportional Gain Adjust
: Programmable
Heat/Cool Deadband Overlap
: Programmable
12.
LINEAR DC OUTPUT (Optional)
: With digital scale and offset,
programmable deadband and update time
4 to 20 mA:
Resolution
: 1 part in 3500 typ.
Accuracy
:
±
(0.1% of reading + 25
mA)
Compliance
: 10 V
(500
W max. loop impedance)
0 to 10 VDC:
Resolution
: 1 part in 3500 typ.
Accuracy
:
±
(0.1% of reading + 35 mV)
Min. Load Resistance
: 10 K
W (1 mA max.)
Source
: % output power, setpoint, deviation, or temperature
(Available for heat or cool, but not both.)
13.
HEATER CURRENT MONITOR (Optional)
:
Type
: Single phase, full wave monitoring of load currents controlled by
main output (OP1)
Input
: 100 mA AC output from current transformer RLC part number
#CT005001 or any current transformer with 100 mA AC output
Display Scale Range
: 1.0 to 999.9 amperes or 100.0%
Input resistance
: 5
W
Accuracy
: 1% of full scale
±
1 LSD (10 to 100% of range)
Frequency
: 50 - 400 Hz
Alarm mode
: Dual acting; heater element fail detect and control device
fail detect
Overload
: 200 mA (steady state)
Minimum output “on” time for Heater break alarm detect
: 400 msec
14.
MOTORIZED VALVE POSITIONER (Optional)
:
Two Outputs
: Valve open and valve close or Linear DC
(optional)
Hardware
: Plug-in, replaceable output modules
Three Inputs
: Slidewire feedback, signal fail detect
(Isolated from main input)
Slidewire resistance
: 100 to 100 K
W
Slidewire exciting voltage
: 0.9 VDC
Slidewire fail action
: programmable
Control mode
: Position mode (with slidewire) and
Velocity mode (w/o slidewire)
Control deadband
: 0.1% to 25.0% (position mode)
0.1 to 25.0 seconds (velocity mode)
Update time
: 1 to 250 seconds
Motor time (open, close)
: 1 to 9999 seconds
Position limits
: Adjustable 0.0 to 100.0% of valve stroke
75