On/off control 66, On/off control – Red Lion TCU User Manual
Page 74
ON/OFF CONTROL
The controller operates in the ON/OFF
control mode by setting the proportional band =
0.0%. The ON/OFF control hysteresis band
(CHYS) parameter eliminates output chatter
around setpoint. For heat/cool systems, the
cooling output can also be used in the ON/OFF
control by setting the relative gain = 0.0
(GAN2). Additionally, the heat/cool parameter
(db-2) determines the amount of operational
deadband or overlap between the two outputs.
Th e phase of the contro l action can be
r e v e r s e d b y t h e o u t p u t c o n t r o l a c t i o n
p a r a me t e r . O N / O F F c o n t r o l i s u s u a l l y
characterized by temperature oscillations about
the setpoint value. Large hysteresis values
make the oscillations larger. ON/OFF control
s h o u l d o n l y b e u s e d w h e r e t h e c o n s t a n t
oscillations are acceptable.
66
Figure 36, OP1 On/Off Action
Figure 37, OP2 On/Off Action
- Data Station Plus (8 pages)
- Data Station Plus (8 pages)
- LDA (16 pages)
- LDSS (8 pages)
- LD (16 pages)
- LDT (16 pages)
- LPAX/MPAX (4 pages)
- EPAX/MPAX (8 pages)
- LDSG (20 pages)
- APS (2 pages)
- APS (2 pages)
- MLPS1 (2 pages)
- AFCM (2 pages)
- Converter Modules (4 pages)
- APMR (4 pages)
- IndustrialPr 6000 Router (2 pages)
- RA 6000 Cellular RTU (2 pages)
- RA 9000 Cellular RTU (186 pages)
- IndustrialPr 6000 Router (2 pages)
- RA 9000 Cellular RTU (3 pages)
- CSMSTRZR (8 pages)
- CSMSTR LE/SX/GT (8 pages)
- CSMSTRV2 (8 pages)
- CSOUT (4 pages)
- CSDIO (8 pages)
- CSINI8 (8 pages)
- CSTC8 (4 pages)
- CSPID (8 pages)
- CSSG (8 pages)
- DLC (28 pages)
- PAX2C (56 pages)
- PAX2C (4 pages)
- PXU (4 pages)
- PXU (32 pages)
- T16 (28 pages)
- TCU (10 pages)
- TSC (8 pages)
- TSC (92 pages)
- P48 (8 pages)
- PCU (8 pages)
- PCU (96 pages)
- PSC (8 pages)
- TLA (16 pages)
- ITMS (16 pages)