Configure module 2 - output parameters (2-op) 41 – Red Lion TCU User Manual
Page 49
Configure Module 2 - Output Parameters (2-OP)
Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
CYCt
Cycle time
0 to 250 seconds
(2)
0 turns OP1 off. This
parameter does not
appear if Valve
Positioner option is
installed.
OPAC
Control Action
drct - cooling
rEv - heating
(rev)
For both PID &
ON/OFF control.
OPLO
Output power lower
limit range
0% to 100%, OP1
(0)
Set OPLO < OPHI
-100% to 100%,
OP1 & OP2
(-100)
If cooling option is
installed.
OPHI
Output power
upper limit range
0% to 100%, OP1
(100)
Set OPHI > OPLO
-100% to 100%
OP1 & OP2
(100)
If cooling option
installed.
OPFL
Sensor fail power
preset
0% to 100%, OP1
-100% to 100%,
OP1 & OP2
(0)
Set to a value to
safely control the
process in the event
of input sensor
failure.
OPdP
Output power
dampening
(filtering) time
0 to 250 seconds
(3)
0 = off
(no dampening) Set
in range of
1
50
to
1
10
of
integral time.
CHYS
ON/OFF control
hysteresis
1 to 250
1 or 0.1 degree
(1)
Heating side only.
tcod
Auto-tune
dampening mode
0 to 4
(0)
0 = fastest response
4 = slowest response
Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
ANAS
Linear DC output
assignment
OP -% output
power
INP - input temp.
SP - setpoint value
dEv - deviation
dE-2 - Internal
Cascade
Secondary
deviation
SP-2 - Internal
Cascade,
Directed
Setpoint
(OP)
This parameter
appears if analog
option is installed.
ANLO
Linear DC output
low scaling value
-999 to 9999
(0.0)
Units depend on
ANAS selection. This
parameter appears if
analog option is
installed.
ANHI
Linear DC output
high scaling value
-999 to 9999
(100.0)
Units depend on
ANAS selection. This
parameter appears if
analog option is
installed.
ANdb
Linear DC output
deadband
0.0 to 25.0%
(0.0)
Only used when
ANAS=OP.
0.0%= no deadband
ANUt
Linear DC update
time
0 to 250 seconds
(0)
Only used when
ANAS=OP.
0 seconds updates
output at a rate of
10/sec.
41