Red Lion TCU User Manual
Page 53
Configure Module 6 - Serial Communications (6-SC)
Unit returns to configuration access point if RS485 serial option is not installed.
Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
bAUd
Baud rate
300 to 9600
(1200)
Baud rate of unit
must match
connected
equipment.
PArb
Parity bit
odd, even, no parity
(odd)
Parity of unit must
match other
equipment.
Add
Unit address
0 to 99
(0)
For multiple units,
each unit must have
a unique address.
Abr
Abbreviated or full
transmission
yes/no
(no)
Selecting yes, the
controller does not
transmit
mnemonics.
PrAt
Auto print rate
0 to 9999
(0)
0 disables auto print
function
PoPt
Print options
yes/no
(no)
Selecting yes allows
print options shown
below, to be
programmed.
INP
Input Temperature
yes/no
(yes)
SEt
Setpoint
yes/no
(yes)
OPr
% Output Power
yes/no
(yes)
Pdb
% Proportional Band
yes/no
(no)
INt
Integral Time
yes/no
(no)
dEr
Derivative Time
yes/no
(no)
AL1
Alarm 1
yes/no
(no)
AL2
Alarm 2
yes/no
(no)
Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
dEv
Deviation From
Setpoint
yes/no
(no)
OFP
% Output Power
Offset
yes/no
(no)
r_P
Setpoint Ramp Rate
yes/no
(no)
Crg
Cooling Relative
Gain
yes/no
(no)
Cdb
Cooling Deadband
yes/no
(no)
OSt
Output Status
yes/no
(no)
rAt
Remote Setpoint
Ratio
yes/no
(no)
bIA
Remote Setpoint
Bias
yes/no
(no)
Pb2
Secondary
Proportional Band
yes/no
(no)
It2
Secondary Integral
Time
yes/no
(no)
dt2
Secondary
Derivative Time
yes/no
(no)
RSP
Remote Setpoint
yes/no
(no)
SP2
Secondary Directed
Setpoint
yes/no
(no)
IN2
Second Analog Input yes/no
(no)
HCr
Heater Current
yes/no
(no)
45