Configure module 4 - alarms (4-al) 43 – Red Lion TCU User Manual
Page 51
Configure Module 4 - Alarms (4-AL)
Unit returns to configuration access point if alarm(s) are not installed.
Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
Act1
Alarm 1 operation
mode
A-HI - absolute high
A-LO - absolute low
d-HI - deviation high
d-LO - deviation low
b-IN - band inside
b-ot - band outside
HCur - heater
break alarm
Valv - valve fail
alarm
A2HI - absolute
high, second
input
A2LO - absolute
low, second input
d2HI - deviation
high, second
input, cascade
d2LO - deviation
low, second
input, cascade
b2IN - band in,
second input,
cascade
b2Ot - band out,
second input,
cascade
(A-HI)
If changed, check
alarm values.
rSt1
Alarm 1 reset mode
Auto - automatic
LAtc - manual reset
(Auto)
Manual reset via
hidden mode
Stb1
Alarm 1 standby
function (delay)
yes/no
(no)
Power-up standby
delay.
AL-1
Alarm 1 value
-999 to 9999
1 or 0.1 degree
(0)
If band alarm
action, then only a
positive value can
be entered.
Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
Act2
Alarm 2 operation
mode
A-HI - absolute high
A-LO - absolute low
d-HI - deviation high
d-LO - deviation low
b-IN - band inside
b-ot - band outside
HCur - heater break
alarm
A2HI - absolute high,
second input
A2LO - absolute low,
second input
d2HI - deviation high,
second input,
cascade
d2LO - deviation low,
second input,
cascade
b2IN - band in,
second input,
cascade
b2Ot - band out,
second input,
cascade
(A-HI)
If changed, check
alarm values.
rSt2
Alarm 2 reset mode Auto - automatic
LAtc - manual reset
(Auto)
Manual reset via
hidden mode.
Stb2
Alarm 2 standby
function (delay)
yes/no
(no)
Power-up standby
delay.
AL-2
Alarm 2 value
-999 to 9999
1 or 0.1 degree
(0)
If band alarm
action, then only a
positive value can
be entered.
AHYS
Alarm Hysteresis
value
1 to 250
1 or 0.1 degree
(1)
Applies to both
alarms. Set to
eliminate chatter.
43