Reference Table: Configuration Parameter Module
Configure Module 1 - Input Parameters (1-IN)
Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
tYPE
Input type
tc-t - Type T TC
tc-E - Type E TC
tc-J - Type J TC
tc-k - Type K TC
tc-r - Type R TC
tc-S - Type S TC
tc-b - Type b TC
tc-N - Type N TC
LIN - Linear mV
display
If changed, be sure to
set the internal jumper
to the appropriate
position.
(jumper in TC
position)
r385 - 385 curve RTD
r392 - 392 curve RTD
rLIN - Linear ohms
display
(tc-J)
(jumper in RTD
position)
SCAL
Temperature
Scale
°F/°C
( °F)
If scale is changed, be
sure to check all
parameters.
dCPt
Temperature
resolution
0 or 0.0
(0)
If resolution changed,
be sure to check all
parameters.
FLtr
Digital filtering
for input
signal
0 to 4
(1)
Increase number for
more filtering effect.
4 = 2/sec display
update rate.
SPAN
Input signal
slope
(correction
factor)
0.001 to 9.999
(1.000)
Normally set to 1.000.
SHFt
Input signal
offset
(correction
shift)
-999 to 9999
1 or 0.1 degree
(0)
Normally set to 0.
SPLO
Lower limit
setpoint range
-999 to 9999
0 or 0.1 degree
(0)
Set low limit below
high limit.
Display
Parameter
Range and Units
(Factory Setting
Value
)
Description/
Comments
SPHI
Upper limit
setpoint range
-999 to 9999
1 or 0.1 degree
(9999)
Set high limit above
low limit.
SPrP
Setpoint ramp
rate
0.0 to 999.9
degrees/minute
(0.0)
0.0 is off (no ramping)
This parameter also
ramps Remote
Setpoint.
InPt
User input
PLOC - Program
disable
ILOC - Integral action
on/off
trnf - auto/manual
select
SPrP - Setpoint ramp
rate on/off
ALrS - Reset alarm
output(s)
Prnt - print request
SPSL - Remote/Local
Setpoint select
(PLOC)
Available on all
nonstandard models
and on standard
models with RS485.
HCur
Heater
Current
Monitor
Scale Factor
0.0 to 999.9 amperes
(50.0)
Scale to current
transformer rating.
40