Output Modules

The main control, optional Alarm, optional Cooling output and optional

Valve Position control output sockets must be fitted with the appropriate
output module. Output modules are shipped separately and must be installed
by the user.

Output Module Restrictions

With some models, the Alarm outputs and Valve Position outputs share the

same common terminal. When using these models, the same type of output
modules are usually installed in these positions.

Installing Output Modules

To install an output module into the controller, remove the bezel assembly

from the case (See

Removing Bezel Assembly

, page 5). Locate the correct

output module socket (OP1, AL1, or AL2/OP2, see Figure 6, Hardware, or
label outside of case) and plug the output module into the socket. No
re-programming is required. If changing an output module type, be sure the
appropriate output interface wiring changes are made. Re-install the bezel
assembly when complete.
Note: For Valve Positioner models, the circuit board markings have the

following meaning:
AL1 - Open Output
AL2/OP2 - Close Output

OP1 - Alarm #1 Output

OUTPUT MODULE “OUTPUT ON” STATE

Relay

Normally open contact is closed.

Logic/SSR Drive

Source is active.

Triac

Solid state switch is closed.

Typical Connections

Relay:

Type:

Form-C

Rating:

5 Amps @ 120/240 VAC or 28 VDC (resistive load), 1/8 HP @

120 VAC (inductive load).

Life Expectancy:

100,000 cycles at maximum load rating. (Decreasing

load and/or increasing cycle time, increases life expectancy).

Logic/SSR Drive:

Type

: Non-isolated switched DC, 12 VDC typical

Drive:

45 mA Max. Can drive multiple SSR Power Units.

6

Figure 3, Relay Module

Figure 4, Logic/SSR Drive Module