Configure module 3 - lockout parameters (3-lc) 42 – Red Lion TCU User Manual
Page 50
Configure Module 3 - Lockout Parameters (3-LC)
Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
SP
Setpoint access
LOC - lockout
rED - read only
Ent - enter
(Ent)
Determines access to
temperature setpoint.
OP
Output power
access
LOC - lockout
rED - read only
Ent - enter
(Ent)
Determines direct
access to output power.
%PW indicator
illuminates when
parameter is selected in
display.
dEv
Deviation
LOC - lockout
rEd - read only
(rEd)
Determines display of
deviation. DEV indicator
illuminates when
parameter is selected in
display.
IN-2
Second Analog
input
LOC - lockout
rEd - read only
(rEd)
Determines display of
Second Analog input
(Remote Setpoint)
(SEC illuminates)
Hcur
Heater Current
LOC - lockout
rEd - read only
(rEd)
Determines display of
Heater Current
(CUR illuminates).
UdSP
Units display
LOC - lockout
rEd - read only
(rEd)
Determines display of F
or C
Code
Access code
0 to 250
(0)
Refer to front panel
disable section for
access levels.
PId
PID values
enable
LOC - lockout
rEd - read only
Ent - enter
(LOC)
Protected mode lockout.
PId2
Secondary PID
values enable
LOC - lockout
rEd - read only
Ent - enter
(LOC)
Protected mode lockout.
Cascade only.
Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
rtbS
Remote Setpoint
Ratio & Bias
LOC - lockout
rEd - read only
Ent - enter
(LOC)
Remote Setpoint Ratio
and Bias values enable
AL
Alarm values
enable
LOC - lockout
rEd - read only
Ent - enter
(LOC)
Protected mode lockout
ALrS
Reset alarms
enable
LOC - lockout
ENBL - enable
(LOC)
Hidden mode lockout
SPSL
Remote/Local
setpoint select
enable
LOC- lockout
ENBL - enable
(LOC)
Hidden mode lockout
trnF
Automatic/Manual
(user) mode
select enable
LOC - lockout
ENBL - enable
(LOC)
Hidden mode lockout
tUNE
Auto-tune enable
LOC- lockout
ENBL - enable
(LOC)
Hidden mode lockout
42