ON/OFF and PID control can be used for the heat and cool outputs in
several combinations.
The following lists the valid control modes:
OP1 & OP2 VALID CONTROL MODES
OP1
MODE
OP2
MODE
MANUAL MODE
OUTPUT POWER
RANGE
OP1
STATE
OP2
STATE
PID
—
0% to +100%
OP1-TP
—
ON/OFF
PrOP = 0.0
—
100
OP1-ON
—
Any other setting
OP1-OFF
—
PID
PID
-100% to +100%
OP1-TP
OP2-TP
PID
ON/OFF
(GAN2=0.0)
0% to +100%
OP1-TP
OP2-OFF
-100% to 0%
OP1-TP
OP2-ON
ON/OFF
(PrOP=0.0)
ON/OFF
(GAN2=0.0)
+100%
OP1-ON
OP2-OFF
-100%
OP1-OFF
OP2-ON
Any other setting
OP1-OFF
OP2-OFF
TP - Time Proportioning
Note: In manual mode, the % output power is not limited to the output
power limits (OPLO & OPHI)
67
Figure 38, OP1/OP2 On/Off Action
See also other documents in the category Red Lion Hardware:
- Data Station Plus (8 pages)
- Data Station Plus (8 pages)
- LDA (16 pages)
- LDSS (8 pages)
- LD (16 pages)
- LDT (16 pages)
- LPAX/MPAX (4 pages)
- EPAX/MPAX (8 pages)
- LDSG (20 pages)
- APS (2 pages)
- APS (2 pages)
- MLPS1 (2 pages)
- AFCM (2 pages)
- Converter Modules (4 pages)
- APMR (4 pages)
- RA 9000 Cellular RTU (186 pages)
- IndustrialPr 6000 Router (2 pages)
- RA 6000 Cellular RTU (2 pages)
- IndustrialPr 6000 Router (2 pages)
- RA 9000 Cellular RTU (3 pages)
- CSMSTRZR (8 pages)
- CSMSTR LE/SX/GT (8 pages)
- CSMSTRV2 (8 pages)
- CSOUT (4 pages)
- CSDIO (8 pages)
- CSINI8 (8 pages)
- CSTC8 (4 pages)
- CSPID (8 pages)
- CSSG (8 pages)
- DLC (28 pages)
- PAX2C (4 pages)
- PAX2C (56 pages)
- PXU (4 pages)
- PXU (32 pages)
- T16 (28 pages)
- TCU (10 pages)
- TSC (8 pages)
- TSC (92 pages)
- P48 (8 pages)
- PCU (96 pages)
- PCU (8 pages)
- PSC (8 pages)
- TLA (16 pages)
- ITMS (16 pages)