beautypg.com

Alarm hysteresis (ahys) 34, Cooling output module (5-02) (optional) 34, Cooling cycle time (cyc2) 34 – Red Lion TCU User Manual

Page 42: Cooling relative gain (gan2) 34, Heat-cool overlap/deadband (db-2) 34

background image

Alarm Hysteresis (AHYS)

The alarm(s) values have a programmable hysteresis band to prevent alarm

output chatter near the alarm trigger temperature. The hysteresis value should
be set to eliminate this effect. A value of 2° to 5° is usually sufficient for most
applications. A single alarm hysteresis value applies to both alarms. See the
alarm action figures, page 29, for the effect of hysteresis on the various alarm
types.

AHYS -

1 to 250 degrees

Cooling Output Module (5-02) (Optional)

The optional secondary output (OP2) operates as an independent cooling

output for systems that use heating and cooling. One of the three types of
output modules (Relay, Logic/SSR Drive or Triac) must be ordered
separately and installed into the cooling channel socket. The output modules
may be replaced or interchanged (with appropriate wiring considerations) at
any time without re-programming the controller.

The front panel indicator OP2 illuminates when the cooling output is

on

.

(See

Output Module “OUTPUT ON” State Table

, page 6, for definition,

under installing output modules section). Cooling output power is defined as
ranging from -100% (full cooling) to 0% (no cooling, unless a heat-cool band
overlap is used).

Cooling Cycle Time (CYC2)

A value of 0 turns off the cooling output, independent of cooling power

demand.

CYC2 -

0 to 250 seconds

Cooling Relative Gain (GAN2)

This parameter defines the gain of the cooling band relative to the heating

band. A value of 0.0 places the cooling output into ON/OFF control mode
with the Heat-Cool parameter (db-2) becoming the cooling output hysteresis.
This may be done independent of the main output control mode (PID or
ON/OFF). Relative gain is generally set to balance the effects of cooling to
that of heating for best control.

GAN2 -

0.0 to 10.0

Example

: If 10 KW of heating and 5 KW of cooling is available, initially set

the cooling gain to (2.0). Figure 18, Heat/Cool Operation illustrates the
effect of different gains.

Heat-Cool Overlap/Deadband (db-2)

This parameter defines the area in which both heating and cooling are

active (negative value) or the deadband area between the bands (positive
value). The parameter units are degrees or tenth’s of degrees (depending on
system resolution). If a heat/cool overlap is specified, the displayed percent
output power is the sum of the heat power (OP1) and the cool power (OP2).

db-2 -

-999 to 9999

If cooling relative gain is zero, the cooling output operates in the ON/OFF

mode, with this parameter becoming the cooling output hysteresis (positive
value only). The Heat/Cool Operation Figures illustrate the effects of
different deadbands.

34

Figure 18, Heat/Cool Operation (db=0)

Figure 19, Heat/Cool Operation (db>0)