Configure module 5 - cooling parameters (5-o2) 44 – Red Lion TCU User Manual
Page 52
Configure Module 5 - Cooling Parameters (5-O2)
Unit returns to configuration access point if cooling option is not installed.
Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
CYC2
Cooling output cycle
time
0 to 250 sec
(2)
0 turns OP2 off.
GAN2
Relative cooling
gain
0.0 to 10.0
(1.0)
0.0 places cooling
output into ON/OFF
control mode and
db-2 becomes
hysteresis value.
db-2
Heating/cooling
overlap-deadband
-999 to 9999
(0)
Positive value is
deadband. Negative
value is overlap. If
GAN2 = 0, this
parameter is cooling
ON/OFF control
hysteresis.
44
See also other documents in the category Red Lion Hardware:
- Data Station Plus (8 pages)
- Data Station Plus (8 pages)
- LDA (16 pages)
- LDSS (8 pages)
- LD (16 pages)
- LDT (16 pages)
- LPAX/MPAX (4 pages)
- EPAX/MPAX (8 pages)
- LDSG (20 pages)
- APS (2 pages)
- APS (2 pages)
- MLPS1 (2 pages)
- AFCM (2 pages)
- Converter Modules (4 pages)
- APMR (4 pages)
- RA 9000 Cellular RTU (186 pages)
- IndustrialPr 6000 Router (2 pages)
- RA 6000 Cellular RTU (2 pages)
- IndustrialPr 6000 Router (2 pages)
- RA 9000 Cellular RTU (3 pages)
- CSMSTRZR (8 pages)
- CSMSTR LE/SX/GT (8 pages)
- CSMSTRV2 (8 pages)
- CSOUT (4 pages)
- CSDIO (8 pages)
- CSTC8 (4 pages)
- CSINI8 (8 pages)
- CSPID (8 pages)
- CSSG (8 pages)
- DLC (28 pages)
- PAX2C (4 pages)
- PAX2C (56 pages)
- PXU (4 pages)
- PXU (32 pages)
- T16 (28 pages)
- TCU (10 pages)
- TSC (8 pages)
- TSC (92 pages)
- P48 (8 pages)
- PCU (96 pages)
- PCU (8 pages)
- PSC (8 pages)
- TLA (16 pages)
- ITMS (16 pages)