beautypg.com

Auto-tune 68, Auto-tune – Red Lion TCU User Manual

Page 76

background image

AUTO-TUNE

Auto-Tune is a user initiated function in which the controller automatically

determines the PID settings based upon the process characteristics. During
Auto-tune, the controller temporarily causes the system to oscillate by
cycling the output power from 0 to 100%. The nature of these oscillations
determines the settings of the controller’s parameters.

Note: If the induced oscillations caused by Auto-tune can cause system problems

or are otherwise unacceptable, the Step Response Manual Tuning Procedure
can be used as a tuning alternative.

Prior to initiating Auto-Tune, it is essential that the controller be

configured to the application. In particular, control hysteresis (CHYS) and
Auto-Tune dampening code (tcod) must be set in the Output Parameters
section. Generally, control hysteresis of 2 - 5 degrees is adequate. The

dampening code may be set to yield the response characteristics shown in
Figure 39, Dampening Code. A dampening code setting of zero gives the
fastest response with possible overshoot, and a code of four gives the slowest
response with minimum overshoot.

The following controller parameters are set by Auto-tune according to the

characteristics of the process:

Proportional Band (ProP)
Integral Time (Intt)
Derivative Time (dErt)
Input Filter (Fltr)
Output Power Dampening (OPdP)

68

Figure 39, Dampening Code

Figure 40, Auto-Tune Operation