beautypg.com

Red Lion TCU User Manual

Page 82

background image

3.

ANNUNCIATORS

:

LED Backlight Status Indicators (Model dependent)

:

%PW

-

Lower auxiliary display shows power output in (%).

DEV

-

Lower auxiliary display shows deviation

(error)

from

temperature setpoint.

OP1

-

Main control output is active.

AL1

-

Alarm #1 is active.

AL2

-

Alarm #2 is active

(for Dual Alarm Option).

OP2

-

Cooling output is active

(for Cooling Option).

OPN

-

Valve positioner OPEN output is active

(for Valve

Positioner option)

.

CLS

-

Valve positioner CLOSE output is active

(for Valve

Positioner option)

.

CUR

-

Lower auxiliary display shows heater current

(for

Heater Current Monitor option)

.

SEC

-

Lower auxiliary display shows second analog input

(for

Second Analog Input option)

.

MAN

-

Flashing: Controller is in manual mode.

REM

-

ON: controller is in remote setpoint mode

(Second Analog Input option).

-

OFF: controller is in local setpoint mode

(Second Analog Input option).

-

Flashing: controller is in Manual control mode

(Second Analog Input option).

4.

CONTROLS

: Four front panel push buttons for modifying and setup of

controller functions and one external input for parameter lockout or other
functions.

5.

MAIN SENSOR INPUT

:

Sample Period

: 100 msec

Response Time

: 300 msec

(to within 99% of final value w/step input;

typically, response is limited to response time of probe)

Failed Sensor Response

:

Main Control Output(s)

: Programmable preset output

Display

: “OPEN”

Alarms

: Upscale drive

DC Linear

: Programmable preset output

Normal Mode Rejection

: 40 dB @ 50/60 Hz

(improves with increased digital filtering).

Common Mode Rejection

: 100 dB, DC to 60 Hz

Protection

: Input overload 120 VAC for 30 seconds.

6.

THERMOCOUPLE

:

Types

: T, E, J, K, R, S, B, N, Linear mV

Input Impedance

: 20 M

W all types

Lead resistance effect

: 20

mV/350W

Cold junction compensation

: Less than 1°C error over 0 - 50°C ambient

temperature range. Disabled for Linear mV type.

Resolution

: 1 °C/F all types, or 0.1°C/F for T, E, J, K and N only.

7.

RTD

: 2, 3 or 4 wire, 100

W platinum, alpha = 0.00385 (DIN 43760), alpha

= 0.003916

Excitation

: 0.175 mA

Resolution

: 1 or 0.1 degree

Lead Resistanc

e: 7

W maximum

8. R

ANGE AND ACCURACY

: Errors include NIST conformity and A/D

conversion errors at 23°C after 20 min. warm-up. Thermocouple errors
include cold junction effect. Errors are expressed as

±

percent of reading

and

±

3/4 LSD unless otherwise noted.

Type

Range

Accuracy

Wire Color (ANSI)

T

-200 to +400°C
-328 to +752°F

0.20% +1.5°C
0.20% +2.7°F

Blue

E

-200 to +750°C
-328 to +1382°F

0.20% +1.5°C
0.20% +2.7°F

Violet

J

-200 to +760°C
-328 to +1400°F

0.15% +1.5°C
0.15% +2.7°F

White

K

-200 to +1250°C
-328 to +2282°F

0.20% +1.5°C
0.20% +2.7°F

Yellow

R

0 to +1768°C
+32 to +3214°F

0.15% +2.5°C
0.15% +4.5°F

Black

S

0 to +1768°C
+32 to +3214°F

0.15% +2.5°C
0.15% +4.5°F

Black

B

+200 to +1820°C
+300 to +3308°F

0.15% +2.5°C
0.15% +4.5°F

Gray

N

-200 to +1300°C
-328 to +2372°F

0.20% +1.5°C
0.20% +2.5°F

Orange

mV

-5.00 to 56.00

0.15% + 1LSD

——

RTD

(385)

-200 to +600°C
-328 to +1100°F

0.10% +0.5°C
0.10% +0.9°F

——

RTD

(392)

-160 to +600°C
-256 to +1100°F

0.10% + 0.5°C
0.10% + 0.9°F

——

Ohms

1.0 to 320.0

0.15% + 1LSD

——

74