beautypg.com

Red Lion GEMINI 33 User Manual

Page 45

background image

Scaling Factor, “K

T

”, effectively becomes the Total Scaling Remaining,

“K

R

”. (K

R

= 0.041667/1 = 0.041667)

If the scaling remaining is between 0.6000 and 5.9999, it can be

programmed directly into the Scale Factor value and the x1 factory setting for

the Scale Multiplier, “SCM”, can be used.

The general rule for choosing a SCM value is, when the Remaining Scaling

Required, “K

R

”, is less than 0.6000, an SCM value of 0.1 or 0.01 can be used

to get a Scale Factor value between 0.6 and 5.9999 or to the point where the

maximum number of significant digits is obtained.

FORMULA #3: SF = K

R

/SCM

Following our continuing example, it is easy to see that the Scaling

Remaining, “K

R

(0.041667), cannot fit into the Scale Factor Value without

losing significant digits. Using the Formula above and a Scale Multiplier

value of 0.01, will allow us to get the maximum number of significant digits

possible (SF = K

R

/SCM = 0.041667/0.01 = 4.1667).

COUNTER SCALING EXAMPLE:

EXAMPLE #1:

A flow sensor provides 62 pulses per gallon. Calculate the scaling required

to provide a display reading in gallons.

In this example the number of “Display Units” is the same as the desired

reading, since there are no decimal points involved.

The number of “Display Units” displayed after 62 pulses have been

counted should be 1.
STEP 1 - Calculate the Total Scaling Factor, “K

T

”, using Formula #1.

K

T

= Display Units/Number of Pulses (Formula #1)

K

T

= 1/62 = 0.016129

STEP 2 - In this application 62 pulses per gallon provides more than enough

resolution, so the “Number of Count Edges” is left set to the factory

configured value of 1. With a “NCE” value of 1, the remaining amount of

scaling necessary is still 0.016129

K

R

= K

T

/NCE (Formula #2)

K

R

= 0.016129/1 = 0.016129

STEP 3 - In order to provide maximum scaling accuracy, a “Scale Multiplier”

value is chosen that will give the maximum amount of significant digits in the

Scale Factor. A value of 0.01 will result in a Scale Factor Value of 1.6129.

SF = K

R

/SCM (Formula #3)

SF = 0.016129/0.01 = 1.6129

EXAMPLE #2:

A quadrature Rotary Pulse Generator that provides 100 pulses per

revolution is coupled to a feed roll that is 2.5 feet in circumference. It is desired

to read in feet with display resolution to the nearest hundredths of a foot.

In this application, the requirement is for the display to read in hundredths

of a foot. A 2.5 ft. distance will equate to 250 “Display Units” (hundredths).

The “Number of Pulses” for 2.5 ft. (250 hundredths) is 100, as stated.

From the information obtained, the Total Scaling Factor, “K

T

”, can be

calculated, using Formula #1.

K

T

= Display Units/Number of Pulses

K

T

= 250/100 = 2.5

With a Total Scaling Factor, “K

T

”, of 2.5, it can easily be seen that for every

pulse that is input, the display will increment by 2.5 display units (hundredths).

The application requires resolution to the nearest hundredth of a foot. In order

to get higher resolution, Quadrature x4 Input Response Mode is selected. This

will provide four times more resolution. Using Formula #2, and 4 for the

“Number of Count Edges”, the Remaining Scaling, “K

R

”, is calculated.

K

R

= K

T

/Number of Count Edges

K

R

= 2.5/4 = 0.625

At this point, it can be seen that the Remaining Scaling value of 0.625 will fit

into the Scale Factor value range without losing any significant digits or

scaling it any further. Because of this, the Scale Multiplier (SCM) factory set

value of x1 is used, and 0.6250 is programmed directly into the Scale Factor,

“SF”.

SF = K

R

/SCM

SF = 0.6250/1 = 0.6250

-43-