beautypg.com

Red Lion GEMINI 33 User Manual

Page 25

background image

SERIAL DIP SWITCH SET-UP

The Serial DIP switches are accessible through the side of the Gemini 3300. A

list of the DIP switch positions and their functions are shown in Figure 4.
BR0 & BR1, BAUD RATE - Set-up is shown in Figure 4, at right. When

changing the Baud Rate, the unit should be powered-down and then powered

back up again. The unit will only recognize a baud rate change upon

power-up, after activating the “Print Request” terminal or after a few

characters have been sent at the new baud rate (If the two previous conditions

have not occurred, the Gemini will see the characters as erroneous and it will

check the baud rate and set itself to operate at the new rate).

PR.ID - PRINT ID. - When this switch is in the up position, the Gemini 3300

will print the unit address, data value ID and the data value when a

transmission is requested. The unit will also insert a 400 msec delay between

transmissions when the “P” command or Print Request terminal is used. This

switch position is generally used when the unit is connected with a printer.

When the switch is in the down position, the Gemini 3300 will transmit

only the data value, without the unit address and data ID. The 400 msec

delay, described above, will not be inserted. This switch position usage is

intended for applications where the Gemini is communicating with a

computer. In these circumstances printing the address and value ID and

inserting a 400 msec print delay is usually unnecessary and needlessly

slows down communication throughput.

PC0, PC1, & PC2, PRINT OPTIONS - Used to control which values are

transmitted when the Print Request terminal is activated or when the

Transmit per Print Options command “P” is sent to the Gemini 3300.

AD0, AD1, AD2 & AD3, UNIT ADDRESS - These switches are used to give

each unit a separate address when more than one unit is connected in the

Loop. See Figure 4, for Switch Set-up.

-23-

FIG. 4: DIP SWITCH SET-UP