beautypg.com

Red Lion GEMINI 33 User Manual

Page 30

background image

ADDITIONAL EMC INSTALLATION GUIDELINES

Although this unit is designed with a high degree of immunity to

ElectroMagnetic Interference (EMI), proper installation and wiring methods

must be followed to ensure compatibility in each application. The type of the

electrical noise, source or coupling method into the unit may be different for

various installations. Listed below are some additional EMC guidelines for

successful installation in an industrial environment.
1. The unit should be mounted in a metal enclosure, which is properly

connected to protective earth.

a. If the bezel is exposed to high Electro-Static Discharge (ESD) levels,

above 4 Kv, it should be connected to protective earth. This can be

done by making sure the metal bezel makes proper contact to the panel

cut-out or connecting the bezel screw with a spade terminal and wire to

protective earth.

2. Use shielded (screened) cables for all Signal and Control inputs. The shield

(screen) pigtail connection should be made as short as possible. The

connection point for the shield depends somewhat upon the application.

Listed below are the recommended methods of connecting the shield, in

order of their effectiveness.

a. Connect the shield only at the panel where the unit is mounted to earth

ground (protective earth).

b. Connect the shield to earth ground at both ends of the cable, usually

when the noise source frequency is above 1 MHz.

c. Connect the shield to common of the unit and leave the other end of the

shield unconnected and insulated from earth ground.

3. Never run Signal or Control cables in the same conduit or raceway with AC

power lines, conductors feeding motors, solenoids, SCR controls, and

heaters, etc. The cables should be run in metal conduit that is properly

grounded. This is especially useful in applications where cable runs are

long and portable two-way radios are used in close proximity or if the

installation is near a commercial radio transmitter.

4. Signal or Control cables within an enclosure should be routed as far away

as possible from contactors, control relays, transformers, and other noisy

components.

5. In very electrically noisy environments, the use of external EMI

suppression devices, such as ferrite suppression cores, is effective. Install

them on Signal and Control cables as close to the unit as possible. Loop the

cable through the core several times or use multiple cores on each cable for

additional protection. Install line filters on the power input cable to the unit

to suppress power line interference. Install them near the power entry point

of the enclosure. The following EMI suppression devices (or equivalent)

are recommended:

Ferrite Suppression Cores for signal and control cables:

Fair-Rite # 0443167251 (RLC #FCOR0000)

TDK # ZCAT3035-1330A

Steward #28B2029-0A0

Line Filters for input power cables:

Schaffner # FN610-1/07 (RLC #LFIL0000)

Schaffner # FN670-1.8/07

Corcom #1VR3

Note: Reference manufacturer’s instructions when installing a line

filter.

6. Long cable runs are more susceptible to EMI pickup than short cable runs.

Therefore, keep cable runs as short as possible.

7. Switching of inductive loads produces high EMI. Use of snubbers across

inductive loads suppresses EMI.

Snubbers:

RLC #SNUB0000

WIRING CONNECTIONS

After the unit has been mechanically mounted, it is ready to be wired. All

conductors should meet voltage and current ratings for each terminal. Also

cabling should conform to appropriate standards of good installation, local

codes and regulations. It is recommended that power supplied to the unit (AC

or DC) be protected by a fuse or circuit breaker. All wiring connections are

made on removable plug-in terminal blocks. There is a separate terminal

block for the bottom board (TBA), relay board (TBB), count inputs (TBC), and

optional Serial Communications (TBD). When wiring the unit, remove the

terminal block and use the numbers on the label to identify the position

number with the proper function. Simply strip the wire, leaving

approximately 1/4" bare wire exposed (stranded wires should be tinned with

solder). Insert the wire into the terminal and tighten down the screw until the

wire is clamped in tightly. Each terminal can accept up to two 18-gage wires.

After the terminal block is wired, install it in the proper location on the PC

board. Wire each terminal block in this manner.

-28-