beautypg.com

Red Lion GEMINI 33 User Manual

Page 31

background image

AC POWER WIRING

For best results, the A.C. power should be relatively “clean” and within the

specified +/-10% variation limits. Drawing power from heavily loaded circuits

or from circuits that also power loads that cycle on and off, should be avoided.

The AC power is connected to the bottom left terminals TBA 1 & 2 marked

AC PWR. The voltage selector switch, located at the side of the unit, is used to

select the proper voltage. The switch is a slide movement type and can be set by

using a small screwdriver. If the switch is toward the rear of the unit, it is set for

115 VAC input. If the switch is towards the front of the unit, it is set for 230 VAC

input. The switch is in the 230 VAC position when shipped from the factory.

Note: Before applying power to the unit, make sure the AC power selector

switch is set for the proper voltage setting.

USING AN EXTERNAL DC POWER SOURCE

The Gemini 3300 can be operated from a D.C. power source that provides

11-14 VDC at the unit’s rated power consumption (700 mA). The power

source can be a 12 V battery or an external power supply that is capable of

supplying the unit’s rated current. It is not necessary to provide battery

backup to retain count information. The Gemini 3300 has an internal

non-volatile memory in which the count and programming information are

stored at power-down. Refer to the “Block Diagram” section.

RELAY WIRING

To prolong contact life and suppress electrical noise interference due to the

switching of inductive loads, it is good installation practice to install a snubber

across the contactor. Follow the manufacturer’s instructions for installation.

Note: Snubber leakage current can cause some electro-mechanical devices

to be held ON.

SERIAL COMMUNICATIONS

The Gemini 3300 can be purchased with a 20 mA Current Loop

Communications Option. On these units, refer to the “Current Loop

Communications” section of the manual, for wiring and operational

procedures of the Serial Loop.

INPUT A & MAGNETIC PICKUP INPUT

The Magnetic Pickup Input and Logic Input A utilize some common

circuitry. For this reason the Input A switches are used to set up both the

Magnetic and Logic Input A. S1 selects between Magnetic Pickup Input and

Logic Input A. WHEN A MAGNETIC PICKUP IS BEING USED, S2 MUST

BE IN THE “SNK” POSITION or the unit will not count.

S3 (HI/LO FRQ) and S4 (HI/LO BIAS) do not effect the Magnetic Pickup

Input and their settings are inconsequential. When S1 is in the Logic position,

the Magnetic Pickup Input is disabled and Input A can be used as a logic input.
Note: A Magnetic Pickup type sensor should not be used unless a signal of

sufficient amplitude is provided at all speeds of operation.

INPUT B

Input B is designed specifically for Logic type inputs. When Input A is set

up for Logic operation, both Inputs A and B operate identically. DIP switch

positions S5, S6, and S7 function the same as S2, S3, and S4.

-29-